Puls UB10.241 UPS Guia De Especificaciones

Descargar
Página de 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
13.  R
ELAY 
C
ONTACTS AND 
I
NHIBIT 
I
NPUT
 
 
The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit. 
 
Relay contacts: 
Ready: 
Contact is closed when battery is charged more than 85%, no wiring failure are recognized, input 
voltage is sufficient and inhibit signal is not active. 
Buffering:  
Contact is closed when unit is buffering. 
Replace Battery: 
Contact is closed when the unit is powered from the input and the battery quality test (SOH test) 
reports a negative result. 
  Relay contact ratings 
max 
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load 
   
min 
1mA at 5Vdc min. 
  Isolation voltage 
max 
500Vac, signal port to power port  
 
 
Signal input: 
7 +
5,1V
3mA
Inhibit
8 -
Inhibit: 
The inhibit input disables buffering. In normal mode, a static signal is 
required. In buffer mode, a pulse with a minimum length of 250ms is 
required to stop buffering. The inhibit is stored and can be reset by 
cycling the input voltage. See also section 27.1 for application hints. 
 Signal 
voltage 
max.  35Vdc 
 Signal 
current 
max.  6mA, current limited 
  Inhibit threshold  
min. 
6Vdc, buffering is disabled above this threshold level 
  
max.  10Vdc 
  Isolation 
nom.  500Vac, signal port to power port 
 
 
 
 
Restriction apply when using the signal and relay contacts in a Haz-Loc environment:  
 
 
The Buffering, Ready and Replace Battery contact is intended to be used for a separately investigated nonincendive field wiring 
and/or field wiring apparatus. The DC-UPS may be located in a Class I, Division 2 (Group A, B, C or D) hazardous (classified) 
location. Associated apparatus must be installed in accordance with its manufacturer's control drawing and Article 504 of the 
National Electrical Code (ANSI/NFPA 70) for installation in the United States, or Section 18 of the Canadian Electrical Code for 
Installations in Canada.  
Selected associated apparatus must be third part listed as providing nonincendive field circuits for the application, and have Voc 
not exceeding Vmax, Isc not exceeding Imax. 
 
Non associated nonincendive field wiring apparatures shall not be connected in parallel unless this is permitted by the associated 
nonincendive field wiring apparatures approval.  
 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 