Weed Instrument MX420-OP4 Output Module Guia De Especificaciones

Descargar
Página de 2
  
Operation & Installation 
Description: 
4 to 20mA, Analog Output Modules, 
Models MX420-OP2 and MX420-OP4,  are designed 
to  provide  two or four channels of process loop 
outputs. 
The input signals from the mated 
MX420-
IP2 or MX420-IP4
4  to  20mA  Input Module on the 
opposite end of the fiber link are digitized and passed 
to its MX Base Module where they are multiplexed 
and converted to a fiber optic signal. 
 
The MX Base 
Module at the output end of the fiber link de-
multiplexes the signals and passes them to a Model 
MX420-OP2 or MX420-OP4,  4  to  20mA, Analog 
Output Modules for conversion back to their original 4 
to  20mA  format.  Or use MX010-OP2  and  MX010-
OP4,  0  to  10Vdc, Analog Output Modules  for 
conversion to the 0 to 10Vdc format. 
Absolutely no field adjustments are required as all 
units deliver the highest degree of accuracy over their 
entire specified ambient temperature range.  
Assembly: Place the top lip of the module's mounting 
channel onto the DIN rail.  Push the lower portion of 
the module towards the mounting surface until it 
"clicks" and locks into place.  Firmly slide the modules 
together such that the module sides are touching 
ensuring a good connection of the  10+2  integrated 
BUS interconnection at the rear of the modules.  
Install End Clamps (Model 2A09) to both sides of the 
module bundle to prevent accidental unplugging of the 
BUS interconnections.  The End Clamps can provide 
convenient screw terminals for connecting the DIN rail 
to Protective Earth (PE) ground. 
Dismantle:  Remove the End Clamps from the DIN 
rail.  Disconnect the BUS interconnections by sliding 
the modules at least 1/2" apart from each other.  Insert 
a screwdriver into the rectangular hole in the metal 
mounting latch at the bottom of the module.  Pushing 
up on the screwdriver's handle causes the latch to 
move downward and disengages it from the DIN rail.  
Tilt the module up and lift it off of the DIN rail. 
 
 
 
Power Requirements 
15 to 30VDC via the interconnection Bus from an 
MX Base Module (MXB-MM2, MXB-SM15, MXB-
SM40 or MXB-SM80) 
MX420-OP2 
90mA @ 24Vdc 
MX420-OP4 
130mA @ 24Vdc  
 
Connections 
Pluggable, Cage Clamp Screw Terminal Blocks, 
Accept 12 to 24 AWG 
MX420-OP2 
2 – 4-20mA Process Loop Ports 
MX420-OP4 
4 – 4-20mA Process Loop Ports 
 
Update Rate
 
57.6KHz, independent of number of modules or 
ports utilized 
 
Operating Range 
3.8 to 20.5mAdc
 
< 3.36mA = Saturation 
< 3.52mA = LED Off 
< 3.8mA = Under Range; LED flashing red 
> 20.5mA = Over Range; LED solid red 
> 21.6mA = Saturation
 
 
Conversion – Voltage to Current
 
4mA = 0Vdc; 20mA = 10Vdc  
Scale: 1mA = 0.625Vdc 
 
Ambient Conditions 
-40 to 85°C 
0 to 95% Humidity (Non-condensing) 
 
Reference Accuracy
 
0.01% @ 25°C
 
Ambient Temp. Effect 
0.08% / 50°C Change 
Max. Loop Resistance
 
600 Ohms 
Signal Resolution
 
16 bit
 
Sensitivity
 
2
16 
or 65,536 Steps
 
 
Mounting 
35mm DIN Rail 
Weight 
< 9oz 
Enclosure Material 
Polyamide 
Flammability Rating 
UL 94V-0 
 
Fuse 
500mA 125V 
Replacement fuses can be purchased from your 
Schurter distributor.  Part number 3403.0163.11 
 
Specifications 
Settings & Indicators 
Use a small screwdriver to press on the latches 
(indentations) at the top and bottom of the front 
housing cover.  Slide housing forward to open. 
       
  
 
MODULE ADDRERSS SETTING: A two position DIP 
switch, SW1, is used to set the 
address of the module 
and it must 
match the address of its mating module at 
the 
opposite  end of the fiber link.  Do not  set two 
modules at the 
same end of the fiber link in one stack 
to the same address setting.  Each module in a stack 
must have a different address to function properly. 
The 4 possible address settings are: 
Address 
SW1-1 
SW1-2 
00 
OFF 
OFF 
01 
OFF 
ON 
10 
ON 
OFF 
11 
ON 
ON 
 
LED 
Color 
Description 
Power 
Green 
Power Applied 
Off 
No Power 
I/O Ports 
Green 
Normal Operation 
Off 
No Input/Output Data 
 
 
Regulatory Information 
INDUSTRIAL CONTROL EQUIP. FOR HAZ. LOC. 
CLASS I, DIVISION 2, GROUPS A,B,C, & D, T4 
Do not disconnect equipment unless area is known to 
be non-hazardous. Certified components for use in a 
suitable enclosure.  Substitution of components or 
other equipment  modification may impair suitability. 
Ambient Temperature:  -40 .. 85C Max 
Electrical Rating:  24Vdc, 130mA 
 
                  
                  
 
FM11ATEX0067X 
II 3 G Ex nA IIC T4 Ta = -40 ºC to 85 ºC 
Service 
Service of this equipment is to be performed by Ultra 
Electronics, NSPI only.  This unit has no scheduled 
replacement of parts.  For installation manuals in a 
community language other than English please 
contact Ultra Electronics, NSPI.