Puls ML15.241 Power Supply Guia De Especificaciones

Descargar
Página de 21
 
 
ML15.241
 
 
MiniLine 
 
24V,
 
0.63A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
22.3.  C
HARGING OF 
B
ATTERIES
 
The power supply can be used to charge lead-acid or maintenance free batteries. (Two 12V batteries in series) 
Instructions for charging batteries (float charging): 
a) 
Ensure that the ambient temperature of the power supply is below 45°C 
b) 
Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge 
voltage. 
End-of-charge voltage 
27.8V 27.5V 27.15V 
26.8V 
Battery 
temperature  10°C 20°C 30°C 40°C 
c) 
Use a 1A or 2A circuit breaker (or blocking diode) between the power supply and the battery. 
d) 
Ensure that the output current of the power supply is below the allowed charging current of the battery. 
e) 
Use only matched batteries when putting 12V types in series. 
f) 
The return current to the power supply (battery discharge current) is typ. 15mA when the power supply is 
switched off (except in case a blocking diode is utilized). 
 
22.4.  E
XTERNAL 
I
NPUT 
P
ROTECTION
 
The unit is tested and approved for branch circuits up to 20A. An external protection is only required, if the supplying 
branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local 
regulations might apply. 
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of 
the circuit breaker. A minimum value of 10A B- or 6A C-Characteristic breaker should be used 
22.5.  P
ARALLEL 
U
SE TO 
I
NCREASE 
O
UTPUT 
P
OWER
 
ML15.241 power supplies can be paralleled to increase the output power. This 
power supply has no feature included which balances the load current 
between the power supplies. Usually the power supply with the higher 
adjusted output voltage draws current until it goes into current limitation. This 
means no harm to this power supply as long as the ambient temperature stays 
below 45°C. The ML15.241 can also be paralleled with power supplies from 
MiniLine series with 24V output voltage. The output voltages of all power 
supplies shall be adjusted to the same value (±100mV). A fuse or diode on the 
output of each unit is only required if more than three units are connected in parallel. If a fuse (or circuit breaker) is 
used, choose one with approximately 150% of the rated output current of one power supply. Keep an installation 
clearance of 15mm (left / right) between two power supplies and avoid installing the power supplies on top of each 
other. Do not use power supplies in parallel in mounting orientations other than the standard mounting orientation 
(input terminals on the bottom and output terminals on top of the unit). Pay attention that leakage current, EMI, 
inrush current, harmonics will increase when using multiple power supplies. 
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Oct. 2009 / Rev. 1.2  DS-ML15.241-EN 
All parameters are specified at 24V, 0.63A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
17/21