Puls QS5.241 Power Supply Guia De Especificaciones

Descargar
Página de 26
 
 
QS5.241, QS5.241-A1
 
 
Q-Series 
24V,
 
5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
4.  DC-I
NPUT
 
 
DC input 
nom. 
DC 110-300V 
±20% 
DC input range 
min. 
88-360Vdc 
continuous operation 
DC input current 
typ. 
1.19A / 0.44A 
110Vdc / 300Vdc, at 24V, 5A 
Allowed Voltage L/N to Earth 
max. 
375Vdc 
IEC 62103 
Turn-on voltage 
typ. 
80Vdc 
steady state value 
Shut-down voltage 
typ. 
76Vdc 
steady state value 
 
 
Fig. 4-1   Wiring for DC Input 
 
Instructions for DC use: 
 
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N
 
 
a)  Use a battery or similar DC source. 
For other sources contact PULS 
b)  Connect +pole to L and –pole to N. 
c)  Connect the PE terminal to a earth wire or to the machine 
ground. 
 
 
5.  I
NPUT 
I
NRUSH 
C
URRENT
 
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short 
input voltage interruptions. 
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Inrush current 
max. 
15A
peak
 15A
peak
 15A
peak
 
over entire temperature range 
 typ. 
8A
peak
 9A
peak
 11A
peak
 
over entire temperature range 
Inrush energy 
max. 
1A
2
s 1A
2
s 1A
2
over entire temperature range 
 
 
Fig. 5-1   Input inrush current, typical behavior 
 
 
 
>
>
Input Current
Input Voltage
Output Voltage
 
 
 
Input:  
230Vac 
Output:  
24V, 5A 
Ambient: 25°C 
Upper curve: 
Input current 5A / DIV 
Middle curve: 
Input voltage 500V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time basis:  
40ms / DIV 
 
Mar. 2013 / Rev. 2.2 DS-QS5.241-EN 
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/26