Installation and Maintenance Manual
24
(b) Enter the Manager Gateway’s IP
Address.
(c) Enter the default user name: admin and
password: admin, and click OK.
(d) Click on the Uncommissioned Nodes
tab
5. Hold the IrDA reader such that it is pointing
directly at the infrared transceiver window
(below the bottom LED) on the wSIM or
Repeater to be commissioned to the
Manager Gateway. It must be held in place
pointing
(below the bottom LED) on the wSIM or
Repeater to be commissioned to the
Manager Gateway. It must be held in place
pointing
at
the
window
for
the
commissioning process to be successful.
6. Hold the magnet wand for 1 second above
the top LED to activate the IrDA
communications. You will see the LEDs blink
in a sweeping pattern from top to bottom
and
communications. You will see the LEDs blink
in a sweeping pattern from top to bottom
and
back
indicating
the
IrDA
communications
are
on.
The
IrDA
communications will remain active for 20
seconds. If the device is not commissioned
during this time frame the node will need to
be swiped with the magnet wand again to
initiate the process.
seconds. If the device is not commissioned
during this time frame the node will need to
be swiped with the magnet wand again to
initiate the process.
7. Click on the Commission Nodes button. You
will observe the IrDA icon in the tool tray
change. The MAC address of the nodes will
be displayed in the window. The
“Successfully transmitted message” text will
appear next to the node. The process takes
change. The MAC address of the nodes will
be displayed in the window. The
“Successfully transmitted message” text will
appear next to the node. The process takes