A.1  EnOcean serial protocol 
When the receiver is in “Serial Interface” mode, it transfers out data blocks of information 
from the received RF telegrams. As long as no transmitter has been learned, all received 
EnOcean telegrams are transferred. As soon as at least one transmitter has been learned 
only telegrams of transmitters learned by the receiver are transmitted via the serial inter-
face. The data block format is explained later in this document; it depends on the type of 
sensor from which the telegram has been received. 
 
A.1.1  Message format 
 
The following figure shows the message format. A block is composed of 2 synchronization 
bytes, 1 byte for the header and N bytes for the message data. 
 
 
Message format for asynchronous serial communication 
 
A.1.2  Byte signals and bit order 
„ 
9600 bps; 8 data bits, no parity bit, one start bit, one stop bit 
„ 
Line idle is binary 1 (standard) 
„ 
Each character has one start bit (binary 0), 8 information bits (least significant bit first) 
and one stop bit (binary 1) 
 
 
 
 
 
 
 
 
 
 
 
 
Signals and bit order sending a byte 
 
 
 
 
 
 
 
 
  TxD 
Sync 
Header 
Byte0 
ByteN-1 
... 
Sync 
 
D0 
STA 
D1  D2  D3  D4  D5  D6  D7  STOP 
TxD 
5V 
0V 
Bit  
Time 
Bit  
Time 
Bit  
Time 
Byte