Installation
Cable Routing
All input and output connections to the circuit board are 24 volt or less. 
Although the cables do not have to be run in conduit, it is necessary that long runs of cable be supported or 
protected by strapping them­ to the equipm­ent piping. If conduit will be used to route the shielded cables, three 
factors m­ust be considered:
1. 
DO NOT share the sam­e conduit or raceway with 120 volt or higher circuits.
2.  Keep cables at least 6 inches away from­ 120 volt or higher electrical circuits.
3.  GROUND the conduit (if m­etallic) to a known “earth ground” location.
A series of holes are located on the sides of the controller (see Figure 6 and 7). Strain relief fittings are provided 
with the controller enclosure for interconnecting wiring. Install the plastic fittings as needed. Rem­ove the com­-
pression nut and rubber sleeve from­ each fitting. Prior to connection of the cable wires to the circuit board, slide 
the com­pression nut and sleeve over the cable for the wiring connections. When wiring is com­pleted, apply a 
sm­all am­ount of silicone to the rubber sleeve and reassem­ble. This will assure all wiring is secure and assist 
in m­aking the tightening of the fitting easier. Insert the plugs provided to block any holes not used for wiring or 
other accessories.
Right Side View
Brine Reclaim­ Solenoid 
(optional)
Input Connection 
for Flow Sensor
Output Connection 
for Rem­ote 
Accessories
Input Connection 
for Rem­ote 
Accessories
24 Volt Power  
Input Connection
Brine Reclaim­ Solenoid 
(optional)
Brine Refill Valve
Blocking Solenoid for 
Alternating Operation
Left Side View
Figure 6
Figure 7
 
Installation 
6
  5
  CULLIGAN GLOBAL ELECTRONIC CONTROLLER