Brivo Systems Inc. ACS300-1 Manual De Usuario
Brivo ACS300 Installation Manual
Page 12
© 2017 Brivo Systems LLC. All rights reserved.
Rev 1
The ACS300 Tamper On/Off Toggle in the off position deactivates both optical
and physical tamper switches.
and physical tamper switches.
Tamper Switch and Optical Tamper Sensor Locations
If there is no reflector present, the optical tamper will not activate. The presence of the optical reflector is
required for this functionality.
required for this functionality.
OPTIONAL: Connect the physical tamper switch to the ACS300.
If the ACS300 unit is installed within an external metal chassis (i.e., ACS6000-EXP), the option for
attaching an external physical tamper switch is provided.
attaching an external physical tamper switch is provided.
Connect the physical tamper switch to the ACS300.
Connect Tamper Switch to the ACS300
b) The tamper header connects to the supplied tamper switch.
c) The header connector for the tamper switch should be connected to the
TAMPER pins located on the upper right side of the ACS300.
NOTE: If the tamper switch is not going to be used, leave the supplied
jumper on this connector to keep the circuit closed.