USER MANUAL FOR COMFLEX-6800  
 
ENU STATUS : 1-0-0 
Copyright - refer to title page 
Page 45 
 
 
 
 
Remote Unit Management Screen 
 
Click RU photo, users can visit RU directly. Make sure two steps are done before visit RU: 
  RU and MU are connected by optical fiber. 
  RU device scanning is done. Note: Go to [Commissioning] page or [Management] page for device 
scanning. 
 
Figure 45: RU Device 
 
NOTE: There are three statuses for PA Service: NormalRecovery and Shutdown. If PA output power 
or reflected power exceeds the threshold (48dBm), software will trigger Recovery:  
  It will reset PA and then re-detect the PA output power and reflected power, if they are normal, the 
PA Service Status will turn to Normal, if PA output power or reflected power is still over the threshold, 
PA Service Status will turn to Recovery again. 
  If PA output power or reflected power is still over the threshold after six times of PA Recovery, PA 
Service  status  will  be  Shutdown  which  will  need  to  be  reset manually.  Reset at  Management  >  PA 
Reset.