Install Hardware
After all devices are configured and connected to the RS-485 network, the baud rate can be
increased to the highest supported rate (some experimentation might be required).
4.7 SINGLE-DOOR CONTROLLER INSTALLATION
The 4G Lite devices incorporate an internal relay that enables them to operate a
deadbolt/door strike directly.
WARNING
The internal relay is limited to a maximum current of 1A. If the
deadbolt/ doorstrike to be controlled draws more than 1A, damage to
the device may occur. If the deadbolt/door strike load exceeds 1A,
an external relay must be used, as described below. Do not use the
same power supply to power a 4G V-Series device and a door
strike.
Assuming the current drawn by the deadbolt/door strike is less than 1A, the connections
between 4G Lite device, deadbolt/door strike, and power supply for the deadbolt/door strike
should be made. Note that a snubber diode (1N4007 or equivalent) must be connected
across the deadbolt/door strike to protect the DC power supply from inductive kickback.
CAUTION
The snubber diode and DC power supply for the deadbolt/door strike
are not supplied with the 4G Lite device. The power supply should
be specified in accordance with the voltage and current
requirements of the deadbolt/door strike, but it must be ensured that
the current to operate the dead bolt/door strike does not exceed 1A.
If the current required to operate the deadbolt/door strike exceeds 1A, an external relay must
be used in conjunction with the 4G V-Series device. The external relay must be specified so
that its contacts are rated to carry the current required by the deadbolt/door strike, and that
the current required to operate its energizing coil is within the 1A capacity of the 4G V-Series
device's internal relay.