FreeWave Technologies Inc. 121819DEE521 Manual De Usuario
LRS-455-EU Data Transceiver Users Manual
LUM0032AA Rev A
Version 1.0
10
the radio will wait for 6 slots, gathering data up the whole time. At the end of the 6 slots, the radio will
send all received data in one “burst”. This is the appropriate setting for most Modbus RTU devices.
With a setting of 2 and higher, the radio will wait for a number of slots calculated by the following formula:
(Modbus RTU Setting + Master Packet Repeat Setting + 1) x 2
For example, in a radio where the Modbus RTU setting = 2 and the Master Packet Repeat setting = 3, the
radio will wait for (2+3+1) x 2, or 12 slots.