NET 
NET 
NET A/B (no polarity)
 
L
ON
W
ORKS
 Data Cables 
• The L
ON
W
ORKS
1
 data cable must be twisted-pair. 
•  In a free-topology configuration, the sum total of the sections must not 
exceed 500m. 
•  In a bus configuration, the sum total of the sections must not exceed 
2700m. 
•  In a free-topology configuration, activate the 50ohm terminator by placing 
the appropriate jumper on the FTT10A plug-in of the CTU-PLG06 board 
inside the TemaServer. 
•  In a bus configuration, place two terminators (with resistance values of 
100ohm 1% ½W) at the two ends of the bus. 
                                                            
1
 L
ON
W
ORKS
®
 is a trademark of Echelon Corporation