FlexSmart™ 609X Series Euro Readers Installation Guide – 6090A-901, Rev A.1
 
System data line terminations may affect the cable required. Contact your system manufacturer for exact 
requirements. Installation should be in accordance with National Electric Code ANSI/NFPA 70. 
Note: The cable should have a minimum of four conductors (two for power and two for output data). If the 
reader’s input control lines are required, then the cable will need to have extra one or two conductors 
depending on the inputs required. 
3.2 Connections 
There is a 6-way connector with detachable terminal block at the rear of the unit. Wire this connector 
according  
 
 
 
 
 
 
 
Figure 3-1 Wiring Connections 
Pins 5 and 6, (LED and buzzer control inputs) may be left unconnected if they will not be used. 
The cable shield/drain should not be connected to anything at the reader end. 
3.3 Grounding 
At the controller end of the cable the shield/drain should be connected directly to an earth ground. An 
earth ground can be established by driving a copper clad ground rod into the earth. If a direct connection 
to a ground rod is not possible, connect the shield/drain to an earth grounded cold water metal pipe or 
steel frame (building beam) that connects to earth. Make certain that the DC resistance between your 
established earth ground and the system ground is 50 ohms or less. Do not connect to a copper fire 
sprinkler system because this may have non-conductive couplings. 
Note: The shield/drain should be connected at the power supply. 
Connection of the shield/drain to an earth ground will provide greater ESD protection of the reader. 
 
Pin 
Reader Wiring 
Pin 6 
Beeper control input 
Pin 5 
LED control input 
Pin 4 
Wiegand data ‘1’/Data  
Pin 3 
Wiegand data ‘0’/Strobe 
Pin 2 
Power supply 0V (ground) 
Pin 1 
Power supply +VE