Crestron Electronics Inc FANDELVEX Manual De Usuario

Descargar
Página de 2
Preliminary
Wiring
The module has flying leads for power and control. Power enters the CLC-FANDELVEX-W 
and passes fan control and light power to the fan. The CLC-FANDELVEX-W has one black 
(hot) and one white (neutral) power input. It also has a red (fan), blue (light), and white 
(neutral) output for control.
NOTE:  Refer to the documentation for the fan to ensure proper fan wiring.
Wiring the CLC-FANDELVEX-W
Power and 
Control 
Output
Power 
Input
AC 110 V 60 Hz
Wall Switch
White
Black
White (Neutral)
Black (Hot)
Red (Fan Power)
Blue (Light Power)
Blue
Black (Motor)
White
White
(Neutral)
Regulatory Compliance
This product is Listed to applicable UL
®
 Standards and requirements by Underwriters Laboratories 
Inc.
Conformité Reglementaire
Ce produit est homologué selon les normes et les exigences UL applicables par Underwriters 
Laboratories Inc.
Federal Communications Commission (FCC) Compliance Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any 
interference received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for 
compliance could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital 
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference when the equipment is operated in a commercial environment. 
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used 
in accordance with the instruction manual, may cause harmful interference to radio communications. 
Operation of this equipment in a residential area is likely to cause harmful interference in which case 
the user will be required to correct the interference at his own expense.
Industry Canada (IC) Compliance Statement
CAN ICES-3(B)/NMB-3(B)
This equipment should be installed and operated with a minimum distance 20cm between the radiator 
and your body Cet équipement doit être installé et utilisé à une distance minimale de 20 cm entre le 
radiateur  et votre corps.
Wireless Communications
The device connects to the Crestron network via the infiNET EX communications protocol. Use 
the procedures outlined below to join or leave an infiNET EX network and to verify 
communications between the device and the control system.
Joining an infiNET EX Network
Before a device can be used in a lighting system, it must first join an infiNET EX network. To join 
an infiNET EX network, the device must be acquired by an infiNET EX gateway.
NOTE:  A device can be acquired by only one gateway.
  1.  Put the infiNET EX gateway into Acquire mode from the unit itself or from Crestron 
Toolbox. Refer to the gateway’s manual at www.crestron.com/manuals for details.
NOTE:  In an environment where multiple gateways are installed, only one gateway 
should be in Acquire mode at any time.
  2.  Put the device into Acquire mode.
 
a.  Tap the ACQUIRE button three times and then press and hold it down 
(tap-tap-tap-press+hold) until the green STATUS LED on the device blinks once (this 
can take up to 10 seconds).
 
b.  Release the button to start the acquire process. The green STATUS LED blinks slowly to 
show that the device is actively scanning the infiNET EX network.
 
•  The green STATUS LED turns on for 5 seconds to show that the device has been 
successfully acquired by the infiNET EX network.
 
•  The green STATUS LED blinks fast to indicate that the device was not successfully 
acquired by the infiNET EX network. Tap the ACQUIRE button to acknowledge the 
failure. Ensure the gateway is in Acquire mode and within range before attempting 
the acquire process again.
  3.  Once all devices have been acquired, take the gateway out of Acquire mode. Refer to the 
gateway’s manual for details.
Leaving an infiNET EX Network
To leave an infiNET EX network, put the device into Acquire mode, as described in “Joining an 
infiNET EX Network” above, when no gateway is in Acquire mode.
Verifying Communications Status
To check the communications status of the device, tap the ACQUIRE button three times and then 
press and hold it down (tap-tap-tap-press+hold) for up to 2 seconds. The green STATUS LED 
blinks to indicate the communications status. Refer to the following table for details.
Crestron Electronics, Inc. 
Installation Guide - DOC. 7705C
15 Volvo Drive   Rockleigh, NJ 07647 
(2045179)
Tel: 888.CRESTRON 
01.18
Fax: 201.767.7576  
Specifications subject to 
www.crestron.com 
change without notice.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to 
the following two conditions: (1) this device may not cause interference, and (2) this device must 
accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio 
exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit 
pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique 
subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
The product warranty can be found at www.crestron.com/warranty.
The specific patents that cover Crestron products are listed at patents.crestron.com.
Certain Crestron products contain open source software. For specific information, please visit 
www.crestron.com/opensource.
Crestron, the Crestron logo, Crestron Toolbox, infiNET EX, and the infiNET EX logo are either 
trademarks or registered trademarks of Crestron Electronics, Inc. in the United States and/or other 
countries. UL and the UL logo are either trademarks or registered trademarks of Underwriters 
Laboratories, Inc. in the United States and/or other countries. Other trademarks, registered 
trademarks, and trade names may be used in this document to refer to either the entities claiming the 
marks and names or their products. Crestron disclaims any proprietary interest in the marks and 
names of others. Crestron is not responsible for errors in typography or photography.
This document was written by the Technical Publications department at Crestron.
©2016 Crestron Electronics, Inc.
MODULE WIRE 
CONNECTION 
White 
Neutral wires to 
the junction box 
and fan 
Black 
Connects to the 
live wire. 
Red 
Connects to the 
fan motor wire. 
Blue 
Connects to the 
lights. 
Error States
The LED blinks a pattern to indicate an error. The patterns listed below are described as 
2-1 or 2-3. For a 2-1 error, an overcurrent condition, the LED blinks twice, pauses for 1 
second, blinks once, pauses for two seconds, and then repeats until the error is 
corrected. During an overcurrent condition, the lights will turn off. Sending a new light 
level corrects the overcurrent condition.
For a 2-3 error, an overtemperature error, the LED blinks twice, pauses for 1 second, 
blinks three times, pauses for two seconds, and then repeats until the error is corrected. 
During an overtemperature condition, the light and fan will turn off. During an 
overtemperature error, requests to turn on the load or fan are ignored. The error clears 
when the device cools.
NOTE:  The overtemperature error is not saved in nonvolatile memory and is cleared 
when power is cycled.
FAN WIRE 
TYPICAL COLOR 
Fan 
Black 
Lights 
Blue 
Neutral 
White 
LED 
COMMUNICATIONS STATUS 
Turns on for 5 seconds 
The device is communicating with the control system. 
Blinks three times 
The device is communicating with the gateway, but the 
gateway is not communicating with the control system. 
Blinks twice 
The device was previously joined to the network but is 
not communicating with the gateway. 
Blinks once 
The device is not joined to the network.