Digital Security Controls Ltd. 02CL3050 Manual De Usuario

Descargar
Página de 28
Skyroute CL3050  Standalone Wireless Communicator
14
Options 3, 4 - Zone Fault, Zone Fault Restores
Modes 2, 3
When the system sees a short circuit across any zone, a zone fault is generated.
DEOL resistors are required for zone fault reporting. In Section [11], Option [2] 
must be set to OFF and Option [3] must be set to ON; In Section [13], Option 3 
must be set to ON and the Skyroute CL3050 must be operating in mode 2 or 3.
Option 3. Default - OFFOption 4. Default - OFF
Options 5, 6 - Zone Tamper, Zone Tamper Restores
Modes 2, 3
When the system sees an open circuit across any zone a zone tamper is gener-
ated. DEOL resistors are required for zone tamper reporting. In Section [11], 
Option [2] must be set to OFF and Option [3] must be set to ON. In Section [13], 
Option [3] must be set to ON and the Skyroute CL3050 must be operating in 
mode 2 or 3.
Option 5. Default - OFF, Option 6. Default - OFF
Option 7 - System Maintenance Events
All Modes
When this option is enabled, the maintenance events enabled in Section [21] are 
transmitted using the codes listed in appendix A.
Default - ON,
Option 8 - Generic Zones
Modes 2, 3
The Skyroute CL3050 supports generic and detailed zone alarm reporting.  By 
default, the Skyroute CL3050 will be in generic zone reporting mode.  When in 
this mode, all zone types are divided into four reporting groups; BA Burg, FA Fire, 
PA Panic, UA Technical.  If any zone from this group initiates a transmission, the 
generic reporting code for this event is sent, additional violations from other 
zones from the same group will be ignored until that group's timer has expired. 
See table below for zone type grouping.
Zone
Type
Detailed 
Reporting Code
Generic 
Reporting Code
Null
Burglary
Fire
Panic
Technical
Gas
Heat
Medical
Emergency
Water
Freezer
Sprinkler
Hold-up
-
BA
FA
PA
UA
GA
KA
MA
QA
WA
ZA
SA
HA
-
BA
FA
PA
UA
UA
FA
PA
PA
UA
UA
UA
PA
Each zone group has it's own timer.  The default time is 5 minutes and is pro-
grammed in Section [23].  If any zone in a group initiates an event, the timer will 
start running and the generic event will be sent.  If any additional zones from the 
same group initiate an event before that group's timer expires, the event will be 
ignored.  This generic zone reporting mode only applies to zone alarms.  Alarm 
restorals, tamper/tamper restorals and fault/fault restorals are not grouped 
together into generic reporting groups.