9 Operation 
Note!  Connect the LC-151 to a positive Voltage output of 9.6 -16VDC source.  
Use only a listed power limited source. 
The detector shall be provided with minimum of 4 hours of standby power from either a 
listed compatible control unit or power supply. 
 
ƒ  The detector begins a 30 second warm up period once connected to power. 
ƒ  If the LEDs are enabled, they will sequentially flash from left to right for the duration of the 30 
seconds warm up period.  
ƒ  Once the warm up period is complete, the detector is ready for use. 
 
 
10 Test procedure  
Walk Test 
IMPORTANT NOTE: Once installed, the unit should be thoroughly tested to verify proper 
operation and coverage. After installation, the unit should be tested annually by the 
installer. The end user should be instructed on how to perform a weekly walk test. 
 
Make sure LEDs control is set to “ON” 
Ensure the detector has completed the 30 second warm up period before walk testing. 
Make sure that the protected area is cleared of all people. 
Create motion in the entire area where coverage is desired by walking perpendicular to the 
detection pattern. 
Look at the LEDs whenever motion is detected - all LEDs are turned ON. 
Allow 5 sec. between each test for the detector to stabilize. 
Walk across the entire area where coverage is desired. Should the coverage be incomplete, 
readjust sensitivity or relocate the detector.  
Once coverage is as desired the LEDs should be disabled.  
 
 
11 Accessories 
 
Device Part 
Number 
Outdoor Mounting bracket 
LC-B1-15X 
PIR Curtain/Long Range  Lens 
LC-L3-15X 
36kg(80lb) PET Filter 
LC-F1-15X