Badger Meter Inc 2014GW-GXY Manual De Usuario

Descargar
Página de 24
Installation Manual
DC Power Source Installation
The gateway can be ordered with a 10-foot DC power source cable (66233-020) for direct connection with a  
customer-supplied DC power source . The power requirements for the gateway are a DC voltage source between 12…24 V DC . 
Power cable lengths may be limited by the voltage of the DC source . Current consumption requirements will vary with the 
type of DC source as follows:
• 
When connecting to a switching AC/DC power source, as with an AC-to-DC power supply, the electrical requirement 
is 500 mA (minimum) @ 15V DC and may be used with a Badger Meter power cable length up to 300 feet long 
(66233-013) .
• 
When connecting directly to batteries, as in the case of a solar assembly, the electrical requirement is 300 mA 
(minimum) @ 12V DC . However, when using 12V DC, the maximum length of the Badger Meter power cable is limited 
to 100 feet (66233-010) due to voltage drop .
Figure 19:  10' DC power cable
OTE:
N
Consult appropriate electrical, building and industry codes, regulations and standards for accepted installation 
practices when attaching the cable to a DC power source .
DC Power Source 
(customer supplied)
10-foot DC Power Source Cable 
with 308 In-line Connector End 
(supplied) 
Power Cable with
308 In-line Connector 
(supplied)
Figure 20:  CDMA or GPRS connection with DC power source (* Shown with NEMA 4 enclosure)
*The enclosure may be recommended but is not included . 
Page 19 
February 2014