Badger Meter Inc 2017OCEV5INTL Manual De Usuario
Installation
ORI-UM-02540-EN-01
ORION endpoint wires:
Red
= Power/Clock; Black = Ground;
Green
= Data
Endpoint
Label
Encoder Connectivity
Endpoint Wire Colors
Red
Black
Green
Reading Resolution
ORION Cellular
INTL
Badger Meter HR-E LCD or HR-E encoders or
E-Series Ultrasonic and Ultrasonic Plus Meter with High
Resolution output
E-Series Ultrasonic and Ultrasonic Plus Meter with High
Resolution output
Enc
oder W
ir
e/T
ermina
tion
Colors
Red
Black
Green
Up to nine (9) most
significant digits
Elster InVISION and ScanCoder® encoders and evoQ4
meter (encoder output)*
meter (encoder output)*
Green
Black
Red
Up to nine (9) most
significant digits
Metron-Farnier Hawkeye*
Red
Black
Green
Up to nine (9) most
significant digits
Mueller Systems 420 Solid State Register (SSR) LCD*
Red
Black
Green
Up to nine (9) most
significant digits
Neptune ProRead, E-coder or ARB-V*
Black
Green
Red
Up to nine (9) most
significant digits
Sensus Electronic Register encoder (ECR) or ICE*
Red
Black
Green
Up to nine (9) most
significant digits
Master Meter® Octave® Ultrasonic meter (encoder output)*
Red
Black
Green
Up to eight (8) most
significant digits
Hersey Translator*
Due to the customized, factory wire configurations of the Hersey
Translator, the terminal posts may not match ORION endpoint wire
colors Please contact Hersey for the terminal post wiring schematic
of your encoders to determine how the posts correspond to ORION
endpoint wires
Translator, the terminal posts may not match ORION endpoint wire
colors Please contact Hersey for the terminal post wiring schematic
of your encoders to determine how the posts correspond to ORION
endpoint wires
OTEE:
N
Competitive encoder output is determined by the encoder configuration
*ORION Cellular endpoints are compatible with the encoders/meters noted above with a manufacture date within 10 years of the current date as long as the
encoder has three wires connected to it and is programmed into the three-wire output mode for AMR/AMI Encoder registers that are currently in two-wire
mode of operation require programming by the Utility, including registers that support auto two- or three-wire detection systems that do not automatically
switch to three-wire mode of operation once a compatible endpoint is connected for ORION connectivity
encoder has three wires connected to it and is programmed into the three-wire output mode for AMR/AMI Encoder registers that are currently in two-wire
mode of operation require programming by the Utility, including registers that support auto two- or three-wire detection systems that do not automatically
switch to three-wire mode of operation once a compatible endpoint is connected for ORION connectivity
The only allowed interconnection of the endpoint to the encoder is the cable provided for interconnection to
passive elements of a water meter This cable provides SELV low voltage limited energy power to the load and
should only be connected to passive elements of water meters
passive elements of a water meter This cable provides SELV low voltage limited energy power to the load and
should only be connected to passive elements of water meters
TO REDUCE THE POSSIBILITY OF ELECTRICAL FIRE AND SHOCK HAZARDS, NEVER CONNECT THE CABLE FROM THE
ENDPOINT OR ENCODER TO ANY ELECTRICAL SUPPLY SOURCE.