Cascade Power Supply
28
Cascade System Modules Operation Guide
OG-CASC-SYS-MOD-1-0-0P
THEORY OF OPERATION
The PSU is designed to offer a stable, low noise, output signal of 48V. The main components are 
the two bricks converting the input voltage into 48V. Mounted on the mainboard (DC-DC -48V to 48V 
Isolated PSU) these bricks are designed for telecommunication purposes and provide the isolation 
required for CASCADE operation. An auxiliary board (-48V to 13.8V Isolated AUX) is also attached to 
the mainboard providing a 13.8V output voltage for external use.
The PSU is designed to be used in a CASCADE subrack with the 
fan assembly running. The PSU is not designed to be used as a 
standalone unit because it requires cooling for normal operations.
Input Filter
The input filter is used to limit the conducted emissions of the power supply and offer filtering for noise 
coming in or out of the PSU.
Temperature Sensors
For temperature monitoring, sensors (U11 and U12)—located close to the bricks—are monitoring 
the 48V board temperature and sending the exact temperature to the microcontroller (U10). The 
microcontroller in turn sends the measurements to the other components of the CASCADE via the 
FIB connection to control the fan speed.
For over-heating, three levels of protection are included:
1. 
Software Protection – if the temperature is too high, the CASCADE fan control system will 
automatically increase the fan speed to lower the internal temperature of the PSU.
2. 
Pre-set Temperature Protection – from the bricks themselves. 
3. 
Thermostats – (48V: Q2, Q4 / 13.8V: Q2) connected to the On/Off connection and at a factory 
preset temperature of 95°C. These thermostats turn the converter OFF if the board temperature 
is higher than the preset temperature.
Voltage and Current Measurement
For the 48V right and left and the 13.8V, the current and voltage is measured independently and the 
information is transmitted to the microcontroller. The microcontroller is comparing the levels within its 
preset nominal levels and enables the corresponding LED in the front of the enclosure. In case of
errors, the alarm light will be ON and the corresponding output LED will be OFF.