7800 Series Keypad Installation Guide
PRELIMINAR
Y
Wiring Specifications for Keypad Bus
When planning a keypad bus installation, keep in mind the following specifications:
1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-
Bus circuits.  Do Not use twisted pair or shielded wire for LX-Bus and keypad bus 
data circuits.  To maintain auxiliary power integrity when using 22-gauge wire 
do not exceed 500 feet.  When using 18-gauge wire do not exceed 1,000 feet.  
Install an additional power supply to increase the wire length or add devices. 
2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless 
of the wire gauge.  This distance can be in the form of one long wire run or 
multiple branches with all wiring totaling no more than 2,500 feet.  As wire 
distance from the panel increases, DC voltage on the wire decreases.
3.  Maximum  number  of  devices  per  2,500  feet  circuit  is  40.   
Note:    Each  panel  allows  a  specific  number  of  supervised  keypads.    Add 
additional keypads in the unsupervised mode.  Refer to the panel installation 
guide for the specific number of supervised keypads allowed.  
4. Maximum voltage drop between the panel (or auxiliary power supply) and any 
device is 2.0 VDC.  If the voltage at any device is less than the required level, 
add an auxiliary power supply at the end of the circuit.  When voltage is too 
low, the devices cannot operate properly.  
Refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031) for more 
information.  Also see the 710/710F Module Installation Sheet (LT-0310).    
Keypad Specifications
MODEL
NORMAL/ 
STANDBY 
CURRENT
ALARM 
CURRENT
FOUR 
ZONES
INTERNAL 
PROX 
READER
WIEGAND 
INPUT
INTERNAL 
DOOR 
STRIKE 
RELAY
7860
184mA
211mA
7863
184mA
211mA
X
7870
184mA + 1.6mA  
per active zone
211mA + 2mA  
per active zone
X
7873
184mA + 1.6mA  
per active zone
211mA + 2mA  
per active zone
X
X
X
X