F10 Installation Manual 
                         Rev. *60          
 
37 of 71
 
Wiring Between F10 Systems for Sync 
Where multiple-antennas are installed, a secondary electronics enclosure is connected to a primary 
via a sync cable. The RF Sync cable is installed prior to configuration. Use 22 AWG 4-conductor 
(STP) (5594) cable for sync cable. Parallel or “Daisy Chain” wiring configuration allows a single 
power supply to operate both units. Use 18AWG plenum-rated cable for the power connection. 
  Caution: If there are more than two (2) electronics enclosures, additional power supplies are required.   
 
Figure 4.7  Multi-Antenna Systems 
Sync Cable and Power Supply Wiring 
1.  Connect the Sync output cable to terminal (J22) to Sync Input terminal (J20) on the secondary 
electronics unit.  
 
Figure 4.8  Sync In / Out 
Terminals  
 
   Note: This would be a combined 
system (with both IN and OUT 
connections made).