Enlighted Inc. SU4E Manual De Usuario

Descargar
Página de 2
Page 2
Page 3
Page 4
Step
Description
1. 
Switch off the circuit breaker supplying power to the light.
2.
Mount the Control Unit (CU) behind the ceiling tile or in a UL 
approved enclosure. Refer to the Control Unit Installation 
Guide
.
3.
Connect the RJ-12 connector end of the Compact Sensor 
cable to the Control Unit.  See Figure 5.
4.
Note: The sensor is designed to mount in a 15/16
th
inch hole 
in the ceiling tile. 
Make a small circular cut in the ceiling tile.   
5.
Pull the 6-pin end of the Compact Sensor cable through the 
hole in the tile. See Figure 2.
6.
Insert the end of the wire into the sensor’s 6-pin connector. 
See Figure 2.
7.
Push the spring arms together and insert the sensor through 
the hole in the tile. See Figure 2.
8.
Turn the power on by switching on the circuit breaker.
Tile Mount Sensor Installation
Figure 2: Tile Mount Sensor
Fixture Mount Sensor Installation
Step
Description
1. 
Switch off the circuit breaker supplying power to the light.
2.
Mount the Control Unit in the ballast cavity of the fixture or 
in a UL approved enclosure.
3.
Connect the RJ-12 connector end of the Compact Sensor 
cable to the Control Unit. See Figure 5.
4.
Note: The sensor is designed to mount in a ½ inch trade size 
knockout on a fixture. 
Determine the location for the sensor in the fixture and cut  
a ½ inch knockout in the fixture. See Figure 3. 
5.
Unthread the spring arms from the Compact Sensor. 
6.
Insert the Compact Sensor through the hole in the fixture. 
Use the spring arms from behind the sensor to fasten the 
Compact Sensor. See Figure 4.
7.
Insert the 6-pin end of the Compact Sensor cable to the 
6-pin connector on the sensor.
8.
Turn the power on by switching on the circuit breaker.
Caution
Installation and maintenance must be performed by a 
qualified electrician in accordance with local, state, and
national electrical codes  (NEC) and requirements.
Spring 
arms
Push the spring 
arms together 
and insert the 
sensor
Figure 5: Wiring Connection
Figure 4: Fixture Mount Sensor
Figure 3: Sensor location
in a fixture
LED Status
Description/Solution
LED not on
Check power and wiring
Purple solid
All LEDs are on during boot time for 5-6 
seconds
Green blinking
Sensor commissioned and working
Red blinking
Incompatibility between LED driver and sensor
– Replace LED driver and if not resolved,  
replace sensor.  
Red solid
Faulty sensor – replace sensor
Green solid
Sensor installed, initialized, and 
uncommissioned – waiting for discovery.
Blue solid
Image being upgraded or BLE Reset
LED Description