Honeywell International Inc. WFSRM Manual De Usuario

Descargar
Página de 68
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C  5/8/2015
39
Device Operations
Wireless Devices
5. The Reset Devices screen appears, displaying the gateway and other devices that have a 
profile assigned. Click to select the desired device and click Reset Device to remove the 
profile.
The profile is removed and the device is reset to the factory default state.
3.6  Device Operations
3.6.1  Modes of Operation
Factory Default Mode
In this mode, the devices are not associated with the gateway. A profile must be assigned to associ-
ate the device with the gateway. For further information on assigning a profile, refer to “Assigning 
a Profile to a Device (Detector or Module) Using a Gateway or Distributor” on page 35. A 
device 
cannot perform any fire protection in the factory default state. In default mode, the devices will be 
viewable in the communicator window of SWIFT Tools with the state displayed as “Factory 
Default”. A device in factory default can be used for site survey.
Site Survey Mode
A site survey assesses and qualifies a site for installing a SWIFT network. The site survey view in 
SWIFT Tools gives the Radio Frequency (RF) assessment of the site. The tool reports the suggested 
device spacing based on the data collected during the site survey. This helps to improve the reliabil-
ity and performance of a SWIFT network in the wireless fire alarm system. A device cannot per-
form any fire protection in the site survey mode. A device that is ready to enter site survey will 
indicate “pending site survey” in the communicator section of SWIFT Tools. A device in site sur-
vey will not communicate with SWIFT Tools and will be listed as “offline” in the communicator 
section. For more information on performing a site survey, refer to Appendix B.
Profile Assigned Mode
In this mode, devices are associated with the gateway but are not active participants in the mesh 
network. A device that is not in the tampered state can join a mesh network in formation or during 
rescue mode. For further information on mesh formation, refer to “Mesh Formation Mode” on 
page 40
. For more information on rescue mode, refer to “Rescue Mode” on page 40. A device with 
an assigned profile can also be used to distribute profiles. Refer to Section 3.5.2. 
Devices are not enabled for fire protection until they become part of a mesh network. A device will 
show an invalid reply or no answer at the FACP. 
In this mode, devices are viewable in the communicator window of SWIFT Tools. If the device has 
a profile and is in the tampered state, it will indicate a status as “Profile Assigned-Tamper”. A non-
tampered device will indicate “active scan” as it searches for a mesh network.
re
se
td
evice_
de
tecto
r.pn
g
Figure 3.8  Reset Devices Screen