UTC Fire & Security Americas Corporation Inc 802A-SHOCK Manual De Usuario

Descargar
Página de 5
Learn Mode Shock Sensor Installation Instructions  
Figure 7: 
Magnet alignment 
 
IMPORTANT!:  If the
 reed switch is not being used; must 
disabled. If the reed switch is enabled but no 
magnet is installed, the sensor will be in a 
continuous alarm state. 
Adjusting the Shock Sensor 
DIP switches 
The following describes the DIP switch functions: 
 
DIP Switches 1 and 2: Adjust the Pulse Count. 
 
DIP Switches 3 and 4: Adjust the sensitivity setting of 
Gross Attack detection. 
 
DIP Switch 5: Enable/disable reed switch. 
 
DIP Switch 6: Not used. 
Note:  In order for the LED to indicate shock detection while adjusting 
the sensitivity, be sure the reed switch is disabled (DIP switch 5 
OFF) or that the magnet is lined up with the reed switch if DIP 
switch 5 is ON. 
Gross Attach Adjustment 
1.  To adjust the sensor for Gross Attack, set DIP switches 1 
and 2 to the ON position. This disables the Pulse Count so 
that the unit can only be activated by a Gross Attack. 
2.  Apply high level shocks to the mounting structure, using 
the LED as a guide to when the alarm trips (LED on for 4 
seconds). The LED will blink for 1 second every time the 
sensor detects a pulse. A shock that is severe enough to 
cause an alarm will cause the LED to light for 
approximately 4 seconds. 
3.  Use switches 3 and 4 to adjust the Gross Attack sensitivity 
of the sensor (see Table 1). 
4.  Repeat step 2 each time a sensitivity change has been 
made. 
Table 1:   Gross attach sensitivity settings 
DIP Switch 3 
DIP Switch 4 
Sensitivity 
OFF 
OFF 
1 (maximum sensitivity) 
ON 
OFF 
OFF 
ON 
ON 
ON 
4 (minimum sensitivity) 
Pulse Count Adjustment 
1.  Set the sensor to the desired Pulse Count (see Table 2 
below). 
Note:   Pulse Count Signals are counted at 1-second intervals and 
stored in a 30-second digital memory. These small signals can 
detect an intruder gently prying open a window or door frame. 
Table 2:  Pulse count adjustment 
DIP Switch 1 
DIP Switch 2 
Adjustment 
OFF 
OFF 
ON 
OFF 
OFF 
ON 
ON 
ON 
Disabled 
2.  To test the pulse count setting, generate small shocks on 
the mounting structure. Each time a shock is detected, a 
pulse is registered in memory and the LED will blink for 
one second. If the programmed pulse count is reached 
within the most recent 30 seconds, the alarm will trip and 
the LED will light for approximately 4 seconds. If the alarm 
trips for any reason, the stored pulses are cancelled. 
3.  Use switches 1 and 2 to adjust the Pulse Count. 
4.  Repeat step 2 each time a sensitivity change is made. 
Reed Switch Setting 
After adjusting the sensor sensitivity, set DIP switch 5 to the 
appropriate setting, ON for enabled or OFF for disabled.