iv. Selecting the menu option Tools > Tamper Clear.
Fig. 3.4: TMSlite “Tamper Clear” menu option
v. Choosing either “UPC Tamper Clear” or “SDC Tamper Clear” from the dialog box drop-
down menu.
Fig. 3.5: TMSlite “Tamper Clear” dialog box
vi. Clicking “Challenge” to display the required challenge token.
(b) Next, the field engineer must log in to the control centre and post the token and the device’s
serial number into an installation authorisation request.
(c) The control-centre operator must now approve the request (if they deem it valid), then
generate an authorisation token and return it to the field engineer.
(d) The field engineer submits the authorisation token to the device by keying it in manually and
clicking “Apply”.
Note:
• The display unit (SDU/SDC) and keypad (UPC) must be connected together throughout this
process.
• The challenge / response operation must be completed within 30 minutes; if not, a new challenge
token must be generated and the process repeated.
The unit itself is now in normal mode and ready for operation. Devices that it is integrated with may
require additional steps; consult product manuals.