X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Configuring a trap destination in the controller using the iReasoning MIBBrowser.
1. In the SNMP tree on the left, go to snmpV2>snmpTargetMIB>snmpTargetAddrTable.
2. Right click this entry and choose table view.
3. Use Create Row to create a new entry. Up to 4 entries are allowed.
4. Give the entry a name in the snmpTargetAddrName e.g. ‘test’
5. Fill in the snmpTargetAddrTDomain: ‘.1.3.6.1.6.1.1’
6. Fill in the required target IP address.
2. Right click this entry and choose table view.
3. Use Create Row to create a new entry. Up to 4 entries are allowed.
4. Give the entry a name in the snmpTargetAddrName e.g. ‘test’
5. Fill in the snmpTargetAddrTDomain: ‘.1.3.6.1.6.1.1’
6. Fill in the required target IP address.
THIS MUST BE DONE IN THE CORRECT FORMAT OR IT WILL NOT WORK.
Example:
We want to use 192.168.3.40.
We put in ‘0xC0 0xA8 0x03 0x28 0x00 0xA2’
7. Fill in the snmpTargetAddrTimeout. Usually 1500 is a good value.
8. Fill in the snmpTargetAddrRetryCount. Usually 3 is a good value.
9. Fill in the snmpTargetAddrTagList. Example group-v2.
10. Fill in the snmpTargetAddrParams. Example v2-params. (This is another table that specifies
8. Fill in the snmpTargetAddrRetryCount. Usually 3 is a good value.
9. Fill in the snmpTargetAddrTagList. Example group-v2.
10. Fill in the snmpTargetAddrParams. Example v2-params. (This is another table that specifies
what parameters are sent with a trap).
11. Fill in the snmpTargetAddrStorageType. This is 2.
12. Press OK. A message ‘SET succeeded’ should appear. The entry should be added to the
12. Press OK. A message ‘SET succeeded’ should appear. The entry should be added to the
table. Traps will now be sent to this destination with the configuration required.