Product feature
SMT750
SMT1000
SMT1500
SMT2200
SMT3000
Output
Power Capacity
500W/750VA
670W/1000VA
980W/1500VA
1980W/2200VA
2700W/3000VA
Nominal Output Voltage
120V
Output Frequency
57-63Hz
Wave Form Type
Sine wave
Output Connections
(6) NEMA 
5-15R
(8) NEMA 5-15R
(8) NEMA 5-15R
(2) NEMA 5-20R
Input
Nominal Input Voltage
120V
Input Voltage Range for main
operations (Max adjustable range)
82-144V (75-154V)
Input Frequency
50/60 Hz +/-3 Hz (auto sensing)
Input Connection
NEMA 5-15P, 6ft cord
NEMA 5-20P
NEMA L5-30P
Batteries and Runtime
Battery Type
Maintenance-free sealed lead-acid battery with suspended electrolyte, leak proof 
Typical Backup Time at 1/2 Load 
(min)
15.9 min
20.6 min
23.9 min
24.1 min
13.6 min
Typical Backup Time at full Load 
(min)
4.6 min
6.1 min
6.7 min
6.7 min
5.5 min
Replacement Battery 
RBC48
RBC6
RBC7
RBC55
Communication and Management
Interface Ports
Serial (RJ45), USB and Smart-Slot
Control Panel and audible alarms
Alpha-numeric LCD display with LED status indicators; alarm on battery, distinctive low battery alarm 
and configurable delays
Emergency Power off (EPO)
Optional
Yes
Surge Protection and Filtering
Surge Energy Rating
459J
480J
Filtering
Full time multi-pole noise filtering: 0.3% IEEE surge let-through, zero clamping response time, meets 
UL1449
Physical
Maximum Height (in)
6.20in
8.50 in
8.50 in
17.0 in
17.0 in
Maximum Width (in)
5.40in
6.70 in
6.70 in
7.7 in
7.7 in
Maximum Depth (in)
14.10in
17.3 in
17.3 in
21.5 in
21.5 in
Net Weight
29 lbs
42 lbs
53 lbs
112 lbs
116 lbs
Conformance
Regulatory
UL 1778, FCC Part 15 Class A, CSA
Warranty and Equipment Protection
Policy
3 years electronics, 2 years battery and $150,000 lifetime EPP