The following table describes the functions of the LCD control buttons.
Table2. Description of control button
Table2. Description of control button
Control
Button
Switch
Function
ON/OFF
--To turn on/off the UPS
Press and hold the button
more than 3 seconds.
--To release the UPS from faulty mode
Cut off input power and then press and hold the
button
button
more than 2 seconds to shut down the
UPS.
UPS Test
Alarm Silence
Alarm Silence
--To perform basic function test
Press and hold the button
for 3 seconds.
--To perform Battery life test
Press and hold the button
for 10 seconds.
-- To disable alarm buzzer
Press the button
for one second.
Select
Press the Select button
to select the settings
value one by one
Enter
-- Enter settings mode
Press and hold the button
more than 3 seconds.
-- Enter settings item
Press and hold the Enter button
more than one
second, the UPS allows users to configure the
settings, and the settings string will flash.
settings, and the settings string will flash.
-- Confirm settings
Press and hold the Enter button
for one second.
-- Exit Settings mode
Press and hold the Enter button
for 3 seconds
or button
for 0.5 second.
Note: Ensure the battery is fully charged during line mode when conducting
functional tests.
Note: A list of events shown as below is not able to disable alarm buzzer:
Low Battery, Fan Failed, Fan Fault Time Out, and Overheat.
Note: User can disable the alarm buzzer when it’s sounding, but an alarm will
still sound when a new alarm event is encountered.