The following table describes the functions of the LCD control buttons. 
 
Table2. Description of control button   
Control 
Button 
Switch 
Function 
 
ON/OFF 
--To turn on/off the UPS 
Press and hold the button 
  more than 3 seconds. 
--To release the UPS from faulty mode 
Cut off input power and then press and hold the 
button 
  more than 2 seconds to shut down the 
UPS. 
 
UPS Test 
Alarm Silence 
--To perform basic function test 
Press and hold the button 
  for 3 seconds. 
--To perform Battery life test 
Press and hold the button 
 
for 10 seconds. 
-- To disable alarm buzzer 
Press the button 
  for one second.   
 
Select
 
Press the Select button 
 
to select the settings 
value one by one 
 
Enter 
-- Enter settings mode 
Press and hold the button 
  more than 3 seconds. 
-- Enter settings item 
Press and hold the Enter button 
  more than one 
second, the UPS allows users to configure the 
settings, and the settings string will flash. 
-- Confirm settings 
Press and hold the Enter button 
  for one second. 
-- Exit Settings mode 
Press and hold the Enter button 
  for 3 seconds 
or button 
  for 0.5 second.
 
 
Note: Ensure the battery is fully charged during line mode when conducting 
functional tests. 
 
Note: A list of events shown as below is not able to disable alarm buzzer:   
Low Battery, Fan Failed, Fan Fault Time Out, and Overheat. 
 
Note: User can disable the alarm buzzer when it’s sounding, but an alarm will 
still sound when a new alarm event is encountered.