6. UPS Maintenance
 
 
6.1 UPS and Battery Care 
For the best preventive maintenance, keep the area around the UPS clean and 
dust-free. If the atmosphere is very dusty, clean the outside of the system with a 
vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of 
25°C (77°F) 
 
6.2 Storing the UPS and Batteries 
When the UPS is intended to store for a long period, recharge the battery every 6 
months by connecting the UPS to utility power. The batteries charge to 90% capacity 
in approximately 4 hours. However, it is recommended that the batteries charge for 
48 hours after long-term storage. 
 
6.3 Time to Replace Batteries 
When LCD backlight turns to red, the screen displays “bTWK” and there is a 
continuous sounding, the battery may need to be replaced. Please check the battery 
connection or contact your local dealer to order new battery. 
 
WARNING:   
 
 
Turn off the UPS and disconnect the utility power cord from the wall outlet. 
 
Servicing should be performed by qualified service personnel knowledgeable 
of batteries and required precautions. Keep unauthorized personnel away from 
batteries   
 
Batteries can present a risk of electrical shock or burn from high short 
circuit current. The following precautions should be observed: 
 
1. Remove watches, rings, or other metal objects. 
2. Use tools with insulated handles. 
3. Do not lay tools or metal parts on top of batteries. 
4. Wear rubber gloves and boots.   
5. Disconnect the charging source prior to connecting or disconnecting battery 
terminal. 
 
 
 
When replacing batteries, replace with the same type and number of 
batteries or battery packs. Contact your service representative to order new