8. Modbus TCP server 
 
8.1.  Modbus TCP frames 
Modbus TCP frames consist of a header and a Modbus request. 
 
Header format: 
Byte Description 
 
Comments 
0 high 
order 
 
Transaction 
identifier 
low order 
 
2 high 
order 
Protocol 
identifier 
low order 
This identifier always equals 0. 
4 high 
order 
Length of data 
low order 
Number of bytes in the Modbus request +1. The frame length is 
always less than 256 bytes, the value of the significant byte 
therefore equals 0. 
Destination identifier (Unit ID)   
7 Modbus request function 
code 
 
 
The frame header returned by the VF-MB1/S15 server is identical to that of the frame 
sent by the client. 
 
 
8.2.  Drive Modbus servers 
The destination identifier (Unit ID) is used to access drive Modbus TCP servers: 
 
Unit ID 
Modbus TCP server 
Accessible parameters 
0-248 
Variable speed drive 
See the VF-MB1/VF-S15 instruction manual. 
251 Option 
board  
255 
IO Scanner 
See the “IO Scanner” section. 
 
 
8.3.  List of Modbus functions supported 
 
 
Function code 
Modbus name 
Description 
Size of data 
03 
Read Holding Registers 
Read N output words 
63 words max. 
06 
Write Single Register 
Write one output word 
16 (0x10) 
Write Multiple Registers 
Write N output words 
63 words max. 
23 (0x17) 
Read/Write Multiple Registers Read/write N words 
(IO Scanning) 
20/20 words max. 
43 (0x2B) 
Read Device Identification Identification