Toshiba IPE002Z Manual De Usuario

Descargar
Página de 89
 
E6581741 
- 71 - 
8.9. Parameter 
data 
It is explanation by the reference method of the list of parameters of the VF-MB1 or 
VF-S15 series as follows. For communication purpose, see the parameter list on 
inverter's instruction manual regarding the communication number, adjustment range and 
so forth. 
 
 
  <Example of excerpts from the inverter’s instruction manual> 
Title 
Communi- 
cation No. 
Function Adjustment 
range 
Minimum 
setting unit 
(Panel/Communi
cation) 
Default 
setting 
Write during 
running 
 
Refer
ence
au
h
- History 
function  Displays parameters in groups of   
five in the reverse order to that in   
which their settings were changed. 
1/1 - 
 
4.3 
5.1 
au
f
0093 Guidance 
function  0 : - 
1 : - 
2 : Preset speed guidance 
3 : Analog signal operation guidance
… 
1/1 0 
Disabled 
 
4.3 
5.2 
au
l
0094 Overload 
 
characteristic  
selection 
0 : - 
1 : Constant torque characteristic 
(150%-60s) 
2 : Variable torque characteristic 
(120%-60s) 
1/1 - 
Disabled 
 
3.5 
5.3 
6.14
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
de
c
0010 
Deceleration time 1 
0.1 to 6000 sec. 
0.1/0.1 *2 
*1 
Enabled 
 
5.2 
ty
0007 
Factory default setting 
0 : - 
1 : 50 Hz default setting 
2 : 60 Hz default setting 
3 : Default setting 1 (Initialization) 
… 
1/1 - 
Disabled 
 
5.20
                                              :
 
 
*1: Default values vary depending on the capacity. 
 
*2: Changing the parameter VR enables to set to 0.01 sec. (adjustment range: 0.01 - 600.0 sec.). 
 
(1)    “Title” means the display on the inverter panel. 
(2)    “Communication number” is affixed to each parameter that is necessary for designating the 
parameter for communication. 
(3)  "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written 
outside the range. The data have been expressed in the decimal notation. For writing the data through 
the communication function, take the minimum setting unit into consideration, and use hexadecimal 
system.  
(4)  "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).   
For example, the "minimum setup unit" of acceleration time (CEE) is 0.01, and 1 is equal to 0.01s. 
For setting a data to 10 seconds, transmit 0x03E8 [10÷0.01=1000d=0x03E8] by communication.   
(5)  Communication numbers "0xxxxA" to "0xxxxF" don't exist in VF-MB1 or VF-S15. 
Therefore, these communication numbers are skipped when read or write. 
For example: 
When the data of two words is read from acc(0009h), 0x000A doesn't exist because of this 
specification.  
Consequently, in this case ACC(0009h) and DEC(0010h) are read.