4.1.1.3 Shutdown when backup time is less than
When the Network Management Card detects that the percentage of backup time remaining is less than the
value set, the shutdown sequence is started.
value set, the shutdown sequence is started.
4.1.1.4 Shutdown duration
Duration required for the systems protected by the Shutdown Modules to shut down (in seconds).
4.1.2 Specific set-up for long autonomy installation (> 30 mn)
For installation where the backup period is longer than 30 minutes, the Network Management Card will initiate
automatically a shutdown at the end of the shutdown timer if this parameter is selected on the “Shutdown
parameters” page.
automatically a shutdown at the end of the shutdown timer if this parameter is selected on the “Shutdown
parameters” page.