Lapara LA-ON-2K-RACK Manual De Usuario

Descargar
Página de 34
 
 
 
www.laparaups.com
LA-ON31-RACK
 
 
Technical specifications 
 
LA-ON-31-RACK SERIES (3PHASE IN / 1PHASE OUT) ON-LINE UPS 
 
MODEL 
LA-ON31-10K-RACK (L)** 
LA-ON31-20K-RACK (L)** 
CAPACITY 
10KVA/8000W 20KVA/6000W 
INPUT 
Low Line Transfer 
176 VAC (phase voltage) ±3 @ 100% load 
110 VAC (phase voltage) ±3 @ 50% load 
Low Line Comeback 
186 VAC (phase voltage) @ 100% load 
120 VAC (phase voltage) @ 50% load 
High line Transfer 
300 VAC (phase voltage)  ± 3% 
Voltage 
range 
High line Comeback 
290 VAC (phase voltage)  ± 3% 
Frequency Range 
46~54Hz at 50Hz / 56~64Hz at  60Hz 
Power Factor 
≧ 0.99  @ 100% load 
OUTPUT 
Output Voltage 
208/220/230/240 VAC 
AC Volt. Regulation (Batt. mode) 
± 1% 
Frequency Range (Synchronized 
Range) 
46~54Hz at 50Hz / 56~64Hz at 60Hz 
Frequency Range (Batt. Mode) 
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz 
Current Crest Ratio 
3:1 
Harmonic Distorion 
≦2% THD (Linear Load) 
≦5% THD (Non-Linear Load) 
AC Mode to Batt.Mode 
Zero 
Transfer time 
Inverter to Bypass 
Zero 
Waveform (Batt. Mode) 
Pure Sinewave 
EFFICIENCY 
AC Mode 
89% 
Battery Mode 
86% 
87% 
BATTERY 
Battery type 
12V / 9AH 
Quantity 
20 pcs. (18-20 pcs adjustable)* 
20pcs x 2strings  (18-20pcs adjustable)* 
Typical Recharge Time 
9 hours recover to 90% capacity 
Max Charging Current 
1A 
Standard 
Model 
Charging Voltage 
273 VDC 
±1% 
Quantity 
Depending on applications 
Quantity 2A 
4A 
Long-run 
model 
Max Charging Current 
273 VDC 
±1% 
INDICATORS 
LCD Display 
UPS status, Load level, Battery level, Input/Output voltage, Discharge time and Fault 
ALARM 
Battery mode 
Sounding every 4 seconds 
Low Battery 
Sounding every second 
Overload 
Sounding twice every second 
Fault 
Continuously sounding 
PHYSICAL 
Dimensions DxWxH 
(mm) 
UPS: 668 x 438 x 133 (3U) 
Battery pack: 580 x 438 x 133 (3U) 
UPS: 668 x 438 x 266 (6U) 
2 x Battery pack: 580 x 438 x 133 (3U) 
Standard 
Model 
Net Weight (Kg) 
UPS: 23 
Battery pack: 63 
UPS: 38 
Battery pack: 63 
Dimensions, DxWxH 
(mm) 
668 x 438 x 133 (3U) 
668 x 438 x 266 (6U) 
Long-run 
model 
Net Weight (Kg) 
23 
38 
ENVIRONMENT 
Humidity 
0-95 % RH at 0- 40°C (non-condensing) 
Noise Level 
< 58dB at 1 m 
< 60 dB at 1 m 
SOFTWARE MANAGEMENT 
Smart RS-232 & USB 
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix & Mac 
Optional SNMP 
Power management from SNMP manager and web browser 
*When using from 18-19 itnernal batteries, the unit will derate according to the following forumula: P = P
Rating
 x (N/20 X 100%) 
** L means Long-run model 
Note 1: Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC 
Note 2: If the UPS is installed or used in a place where the altitude is above 1000m, the output power must be derated 1% per 100m 
Specifications are subject to change without further notice. 
 
- 28 -