Specification 
- Outdoor Units
2013 SAMSUNG System Air Conditioners
15
DVM System
Model Name
DVM S HP
AM200FXVAGH/EU
AM220FXVAGH/EU
AM240FXVAGH/EU
AM260FXVAGH/EU
AM280FXVAGH/EU
AM300FXVAGH/EU
DVM S HR
AM200FXVAGR/EU
AM220FXVAGR/EU
AM240FXVAGR/EU
AM260FXVAGR/EU
AM280FXVAGR/EU
AM300FXVAGR/EU
Power Supply
Ф, #, V, Hz
3,4,380-415,50
3,4,380-415,50
3,4,380-415,50
3,4,380-415,50
3,4,380-415,50
3,4,380-415,50
Mode
-
HP / HR
HP / HR
HP / HR
HP / HR
HP / HR
HP / HR
Performance
HP
HP
20.00
22.00
24.00
26.00
28.00
30.00
Capacity
(Nominal)
Cooling 
kW
56.00
61.60
67.20
73.60
78.60
84.00
Btu/h
191,100
210,200
229,300
251,100
268,200
286,600
Heating 
kW
63.00
69.30
75.60
82.80
87.80
94.50
Btu/h
215,000
236,500
258,000
282,500
299,600
322,400
Power
Power Input
(Nominal)
Cooling 1)
kW
15.19
17.35
16.80
17.30
19.40
21.28
Heating 2)
13.90
16.70
17.40
18.20
20.20
20.60
Current Input
(Nominal)
Cooling 1)
A
24.40
27.80
27.00
27.80
31.10
34.20
Heating 2)
22.30
26.80
28.00
29.20
32.40
33.10
MCA
52.50 (MCA)
55.60 (MCA)
-
-
-
-
MFA
A
75.00
75.00
-
-
-
-
COP
Nominal Cooling 1)
-
3.69
3.55
4.00
4.25
4.05
3.95
Nominal Heating 2)
-
4.53
4.15
4.34
4.55
4.35
4.59
Compressor
Type
-
SSC Scroll x 2
SSC Scroll x 2
SSC Scroll x 2
SSC Scroll x 2
SSC Scroll x 3
SSC Scroll x 3
Output 
kW x n
(6.13x2)
(6.13x2)
(6.13)x2
(6.13) + (6.13)
(6.13) + (4.96x2)
(6.13) + (6.13x2)
Model Name
-
DS-GB066FAVASG x 2
DS-GB066FAVASG x 2
DS-GB066FAVASG x 2
DS-GB066FAVASG x 2
DS-GB066FAVASG x 1 + DS-GB052FAVASG x 2
DS-GB066FAVASG x 3
Oil
Type
-
PVE
PVE
PVE
PVE
PVE
PVE
Initial Charge
cc
4600
4600
4600
4600
6900
6900
Fan
Type
-
Propeller
Propeller
Propeller
Propeller
Propeller
Propeller
Output x n
W
620 x 2
620 x 2
(400 x 1) x 2
400 x 1 + 620 x 2
400 x 1 + 620 x 2
400 x 1 + 620 x 2
Air Flow Rate
CMM
275
295
190 x 2
190 + 260
190 + 260
190 + 270
I/s
4,583.33
4,916.67
3,166.67 x 2
3,166.67 + 4,333.33
3,166.67 + 4,333.33
3,166.67 + 4,500.00
External Static Pressure
Max.
mmAq
8.00
8.00
8.00
8.00
8.00
8.00
Pa
78.45
78.45
78.45
78.45
78.45
78.45
Piping
Connections
Liquid Pipe
Ф, mm
15.88
15.88
15.88
19.05
19.05
19.05
Ф, inch
5/8"
5/8"
5/8"
3/4"
3/4"
3/4"
Gas Pipe
Ф, mm
28.58
28.58
28.58
34.93
34.93
34.93
Ф, inch
1 1/8"
1 1/8"
1 1/8"
1 3/8"
1 3/8"
1 3/8"
Discharge Gas Pipe                                  (HR)
Ф, mm
28.58
28.58
28.58
28.58
28.58
28.58
Ф, inch
1 1/8"
1 1/8"
1 1/8"
1 1/8"
1 1/8"
1 1/8"
Oil Equalizing Pipe 
Ф, mm
-
-
-
-
-
-
Ф, inch
-
-
-
-
-
-
Installation
Limitation
Max. Length
m
200(220)
200(220)
200(220)
200(220)
200(220)
200(220)
Max. Height
m
110(40)
110(40)
110(40)
110(40)
110(40)
110(40)
Field Wiring
Power Source Wire
mm2
-
-
-
-
-
-
Transmission Cable
mm2
0.75 ~ 1.5
0.75 ~ 1.5
0.75 ~ 1.5
0.75 ~ 1.5
0.75 ~ 1.5
0.75 ~ 1.5
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
8.40
8.40
11.00
13.20
12.90
14.20
Sound 
Sound Pressure
dB(A)
65.0 / 87.0
65.0 / 87.0
-
-
-
-
Sound Power
-
-
-
-
-
-
External
Dimension
Net Weight
DVM S HP
kg
300.0
300.0
190.0 x 2
190.0 + 235.0
190.0 + 278.0
190.0 + 300.0
DVM S HR
306.0
306.0
195.0 x 2
195.0 + 241.0
195.0 + 284.0
195.0 + 306.0
Shipping Weight
DVM S HP
kg
319.0
319.0
206.0 x 2
206.0 + 254.0
206.0 + 297.0
206.0 + 319.0
DVM S HR
325.0
325.0
211.0 x 2
211.0 + 260.0
211.0 + 303.0
211.0 + 325.0
Net Dimensions (WxHxD)
mm
1,295 x 1,695 x 765
1,295 x 1,695 x 765
(880 x 1,695 x 765) x 2
880 x 1,695 x 765 + 1,295 x 1,695 x 765
880 x 1,695 x 765 + 1,295 x 1,695 x 765
880 x 1,695 x 765 + 1,295 x 1,695 x 765
Shipping Dimensions (WxHxD)
mm
1,363 x 1,857 x 832
1,363 x 1,857 x 832
(948 x 1,857 x 832) x 2
948 x 1,857 x 832 + 1,363 x 1,857 x 832
948 x 1,857 x 832 + 1,363 x 1,857 x 832
948 x 1,857 x 832 + 1,363 x 1,857 x 832
Operating
Temp. Range
Cooling
°C
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
-5.0 ~ 48.0
Heating
°C
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
-20.0 ~ 24.0
DVM S HP COMPACT MODULE
* Product Specifications in the Publication can be changed without a prior notice. Because there is always an ongoing improvement on our product.
* If you wish to install an outdoor unit module with a capacity of over 60 HP, then please contact your local Samsung Dealer.
* The maximum height of installation limitation for piping connections is only allowable when using PDM kits.