HP BLc3000 696908-B21 Manual De Usuario

Los códigos de productos
696908-B21
Descargar
Página de 33
Enclosure Unit –
Rack Model
Dimensions (H x W x D)
(with bezel)
10.4 x 19.1 x 32.977 in (265 x 485 x 835 mm)
Weight
(approximate)
Maximum
(one enclosure with 8
blades and 4 interconnects
installed)
300 lb (136 kg)
Minimum
(one enclosure without
blades and interconnects)
130 lb (59 kg)
Input Requirements
(per AC power supply)
Rated Line Voltage
90  132 VAC
180  264 VAC
Rated Input Current
9.3 A (at 100 VAC)
9.7 A (at 120VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)
Rated Input Frequency
47 to 63 Hz
BTU Rating
Maximum per power
supply
2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)
Power Specifications
To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL:
Power Supply Output
(per power supply)
Rated Steady-State Power 800 W (at 100 VAC)
900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)
Maximum Peak Power
880 W (at 100 VAC)
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC)
System Inlet
Temperature
Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m (1.8°F
per every 1000 ft) above sea level to a maximum
of 3050 m (10,000 ft), no direct sustained
sunlight. Maximum rate of change is 10°C/hr
(18°F/hr). The upper limit may be limited by the
type and number of options installed. System
performance may be reduced if operating with a
fan fault or above 30°C (86°F).
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
(non-condensing)
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F)
maximum wet bulb temperature, non-
condensing.
QuickSpecs
HP BladeSystem c3000 Enclosure
Technical Specifications
DA - 12790   Worldwide — Version 56 — February 18, 2014