Panasonic CS-RE9PKE-3 Prospecto
Due to the ongoing inno
vation of our pr
oducts, the specifi
cations of this catalogue ar
e v
alid barring typogr
aphic err
ors, and m
ay
be subject to minor modifi
cations b
y the manufactur
er without prior w
arning in or
der to impr
ov
e the pr
oduct. The total or pa
rtial r
epr
oduction of this catalogue is pr
ohibited without the expr
ess authorisation of P
anasonic UK Ltd.
To find out how Panasonic cares for you, log on to: www.aircon.panasonic.eu
Contact Details: Telephone: 01344 853182 / www.panasonic.co.uk/aircon
Address: Panasonic Air Conditioning: Panasonic House // Willoughby Road // Bracknell //
Berkshire // RG12 8FP
Address: Panasonic Air Conditioning: Panasonic House // Willoughby Road // Bracknell //
Berkshire // RG12 8FP
Inverter System. The Inverter range provides
greater efficiency, more comfort and less noise
than classic air conditioners. The Inverter system
provides more precise temperature control, and
keeps the ambient temperature constant .
greater efficiency, more comfort and less noise
than classic air conditioners. The Inverter system
provides more precise temperature control, and
keeps the ambient temperature constant .
A
class
energy saving
Super Quiet Mode. Thanks to its latest
generation compressor and its twin blade
fan, our outdoor unit is one of the most
silent on the market. The indoor unit
emits an almost imperceptible 22 dB.
generation compressor and its twin blade
fan, our outdoor unit is one of the most
silent on the market. The indoor unit
emits an almost imperceptible 22 dB.
SUPER QUIET
Silent air
22 dB
5 Years Warranty. We
guarantee the
compressors in the
entire range for five
years.
guarantee the
compressors in the
entire range for five
years.
5 year
compressor
warranty
www
.eggeassociats.net
WALL MOUNTED RE-3 TYPE
STANDARD INVERTER
STANDARD INVERTER
KIT-RE9-PKE-3 // KIT-RE12-PKE-3 //
KIT-RE15-PKE-3 // KIT-RE18-PKE-3 //
KIT-RE24-PKE-3
KIT-RE15-PKE-3 // KIT-RE18-PKE-3 //
KIT-RE24-PKE-3
HEALTHY AIR
· Odour-removing function
· Anti-mould filter
· Odour-removing function
· Anti-mould filter
ENERGY, EFFICIENCY AND ECOLOGY
· Inverter system
· R410A refrigerant gas
· Inverter system
· R410A refrigerant gas
COMFORT
· Super Quiet mode (for RE9, RE12)
· Powerful mode (for RE9, RE12 and RE15)
· Automatic vertical airflow control
· Hot start mode
· Automatic restart
· Simple change over
· Super Quiet mode (for RE9, RE12)
· Powerful mode (for RE9, RE12 and RE15)
· Automatic vertical airflow control
· Hot start mode
· Automatic restart
· Simple change over
EASE OF USE
· 12-hr timer (only for RE9, RE12 and RE15)
· User friendly infrared remote control
· 12-hr timer (only for RE9, RE12 and RE15)
· User friendly infrared remote control
EASY INSTALLATION AND MAINTENANCE
· Removable, washable panel
· Maintenance access through the top panel
· Removable, washable panel
· Maintenance access through the top panel
of the outdoor unit
· Self-diagnosis function
Kit
KIT-RE9-PKE-3
KIT-RE12-PKE-3
KIT-RE15-PKE-3
KIT-RE18-PKE-3
KIT-RE24-PKE-3
Indoor
CS-RE9PKE-3
CS-RE12PKE-3
CS-RE15PKE-3
CS-RE18PKE-3
CS-RE24PKE-3
Outdoor
CU-RE9PKE-3
CU-RE12PKE-3
CU-RE15PKE-3
CU-RE18PKE-3
CU-RE24PKE-3
Cooling capacity
Nominal (Min - Max)
kW
2.50 (0.90-3.00)
3.50 (0.90-3.90)
4.20 (1.00-4.60)
5.00 (0.98-6.00)
6.80 (0.98-8.10)
Nominal (Min - Max)
kCal/h
2,150 (770-2,580)
3,010 (770-3,350)
3,610 (860-3960)
4,300 (840-5,160)
5,850 (840-6,970)
EER
1)
Nominal (Min - Max)
Energy Saving 3.57 (4.74-3.00)
A
3.47 (5.29-3.25)
A
3.33 (4.76-2.78)
A
3.40 (3.50-2.96)
A
3.24 (2.58-3.03)
A
SEER
Nominal
Energy Saving 5.6
A+
5.6
A+
5.6
A+
6.7
A++
5.9
A+
Pdesign (cooling)
kW
2.5
3.5
4.2
5.0
6.8
Power input Cooling
Nominal (Min - Max)
kW
0.70 (0.19-1.00)
1.01 (0.17-1.2)
1.26 (0.21-1.65)
1.47 (0.28-2.03)
2.10 (0.38-2.67)
Annual electricity consumption (cooling)
2)
kWh
156
219
263
261
403
Heating capacity
Nominal (Min - Max)
kW
3.30 (0.90-4.10)
4.25 (0.90-5.10)
5.00 (0.90-6.80)
5.80 (0.98-8.00)
8.60 (0.98-9.90)
Nominal (Min - Max)
kCal/h
2,840 (770-3,530)
3,660 (770-4,390)
4,300 (770-5850)
4,990 (840-6,880)
7,400 (840-8,510)
Heating capacity at -7°C
Nominal
kW
3.00
3.70
4.93
4.98
6.13
COP
1)
Nominal (Min - Max)
Energy Saving 4.02 (5.29-3.57)
A
3.79 (6.00-3.49)
A
3.61 (4.28-2.98)
A
3.77 (2.88-3.08)
A
3.28 (2.18-3.14)
C
SCOP
Nominal
Energy Saving 3.4
A
3.4
A
3.4
A
4.1
A+
3.4
A
Pdesign at -10 °C
kW
2.5
3.2
3.6
4.4
5.5
Power input Heating
Nominal (Min - Max)
kW
0.82 (0.17-1.15)
1.12 (0.15-1.46)
1.385(0.21-2.280)
1.54 (0.34-2.60)
2.62 (0.45-3.15)
Annual electricity consumption (heating)
2)
kWh
1029
1318
1482
1502
2265
Indoor Unit
Power source
Power source
V
230
230
230
230
230
Recommended Fuse
A
16
16
16
20
20
Recommended power cable section
mm²
1.5
1.5
1.5
2.5
2.5
Connection (indoor/outdoor)
mm²
4 x 1.5
4 x 1.5
4 x 1.5
4 x 2.5
4 x 2.5
Current (Nominal)
Cooling / Heating
A
3.3 / 3.8
4.7 / 5.2
6.0 / 6.3
6.6 / 6.9
9.6 / 11.8
Max. current
A
6.3
8.4
10.5
11.4
13.9
Air Volume
Cooling / Heating
m³/h
750 / 666
750 / 750
822 / 870
978 / 1,074
1,104 / 1,164
Moisture removal volume
l/h
1.4
2
2.4
2.8
3.9
Sound pressure Level
3)
Cooling - Heating (Hi / Lo / S-Lo) dB(A)
42 / 27 / 22 - 42 / 27 / 25
42 / 30 / 22 - 42 / 33 / 25
44 / 31 / 29 - 46 / 34 / 28
44 / 37 - 44 / 37
47 / 38 - 47 / 38
Sound power Level
Cooling / Heating (Hi)
dB
58 / 58
58 / 58
60 / 62
60 / 60
63 / 63
Dimensions
H x W x D
mm
290 x 848 x 213
290 x 848 x 213
290 x 848 x 213
290 x 1,070 x 240
290 x 1,070 x 240
Net weight
kg
8
8
8
12
12
Outdoor Unit
Air Volume
Air Volume
Cooling / Heating
m³/h
1,902 / 1,842
1,956 / 1,896
1,956 / 1,956
2,352 / 2,274
3,012 / 3,012
Sound pressure Level
3)
Cooling / Heating (Hi)
dB(A)
47 / 48
48 / 50
49 / 51
47 / 47
52 / 52
Sound power Level
Cooling / Heating (Hi)
dB
63 / 64
64 / 66
65 / 67
61 / 61
66 / 66
Dimensions
4)
H x W x D
mm
540 x 780 x 289
540 x 780 x 289
540 x 780 x 289
695 x 875 x 320
795 x 875 x 320
Net weight
kg
23
26
27
46
67
Piping connections
Liquid / Gas pipe
inch (mm)
1/4 (6.35) / 3/8 (9.52)
1/4 (6.35) / 3/8 (9.52)
1/4 (6.35) / 1/2 (12.70)
1/4 (6.35) / 1/2 (12.70)
1/4 (6.35) / 5/8 (15.88)
Refrigerant Loading
R410A
kg
0.77
0.86
0.92
1.22
1.8
Elevation difference (in/out)
Max
m
10
10
10
15
20
Piping length
Min / Max
m
3 / 15
3 / 15
3 / 15
3 / 20
3 / 30
Precharge length
Max
m
7
7
7
7.5
10
Additional charge
g/m
20
20
20
20
30
Operating range
Cooling Min / Max
°C
-10 / +43
-10 / +43
-10 / +43
-10 / +43
-10 / +43
Heating Min / Max
°C
-15 / +24
-15 / +24
-15 / +24
-15 / +24
-15 / +24
Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Heating Outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb)
1) EER and COP classification is at 230 V in accordance with EU directive 2002/31/EC. 2) The annual energy consumption is calculated in accordance with the ErP directive. 3) The Sound pressure level of the units shows the value measured of a position 1 meter in front of the main
body and 0,8 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification. 4) Add 70 mm for piping port.
Specifications subject to change without notice.
For detailed information about ErP, please visit our page http://www.doc.panasonic.de
body and 0,8 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification. 4) Add 70 mm for piping port.
Specifications subject to change without notice.
For detailed information about ErP, please visit our page http://www.doc.panasonic.de
Exceptional Seasonal Cooling
Efficiency based on the new ErP
regulation. Higher the SEER ratings
mean greater efficiency. Save all
the year while cooling!
Efficiency based on the new ErP
regulation. Higher the SEER ratings
mean greater efficiency. Save all
the year while cooling!
6.7 A++
SEER
SEASONAL ENERGY
EFFICIENCY RATIO
4.1 A+
SCOP
SEASONAL COEFFICIENT
OF PERFORMANCE
Exceptional Seasonal Heating
Efficiency based on the new ErP
regulation. Higher the SCOP ratings
mean greater efficiency. Save all
the year while heating!
Efficiency based on the new ErP
regulation. Higher the SCOP ratings
mean greater efficiency. Save all
the year while heating!
For RE18 and
RE24. Included
with the indoor
unit
RE24. Included
with the indoor
unit
CS-RE9PKE-3 // CS-RE12PKE-3 // CS-RE15PKE-3
CU-RE9PKE-3
CU-RE12PKE-3
CU-RE15PKE-3
CU-RE12PKE-3
CU-RE15PKE-3
CU-RE18PKE-3
CU-RE24PKE-3
For RE9, RE12
and RE15.
Included with
the indoor unit
and RE15.
Included with
the indoor unit