3
Adding or Removing Components 
Adding or Removing a Battery String
Disconnect power to the system
Connect the new battery string
Warning
When adding or removing a battery string, first disconnect 
power to the Battery Management System by unplugging the 
power input cable to avoid causing sparks that could cause 
a battery to explode.
See also
See the installation guide (990-1224B), which came with your 
system, for battery string connection instructions. It is also 
available on the APC Web site (www.apc.com).
The Battery Management System auto-detects the new 
battery string. Verify that the polarities of the two strings 
match. If they do not, the Battery Management System will 
not be able to detect the second string.