Bosch D265AW Manual De Usuario

Descargar
Página de 3
Certifications and approvals
Region
Certification
USA
UL
UROX: Smoke - Automatic Fire Detectors
(UL268 and A)
CSFM
see our website
Hong Kong
HKFSD
Installation/configuration notes
Mounting
The detector head is part of a compound device. The
detector base contains all the wiring. The detector
head attaches to the base by aligning the head with
the base and turning it clockwise. No tools are
required for installation other than the hex key used to
tighten the tamper screw.
Wiring
For detailed wiring requirements, see the D261AW
Detector Base Datasheet
.
Parts included
Quanti
ty
Component
1
Detector head with dust cover
Technical specifications
Environmental Considerations
Temperature (operating):
+32°F to +120°F (0°C to +49°C)
Mechanical Properties
Dimensions (diameter x D):
4 in. x 1.25 in. (10.2 cm x 3.2 cm)
Power Requirements
Current (alarm):
150 mA maximum
Current (standby):
0.038 mA at 12 VDC
0.055 mA at 24 VDC
Current (surge):
0.2 mA
Voltage (input):
12 VDC or 24 VDC nominal;
8 VDC to 35 VDC operating range
Ordering information
D265AW Photoelectric Smoke Detector Head
Detects the large smoke particles that typically result
from wood, paper, and fabric combustion
Order number 
D265AW
 
2 | D265AW Photoelectric Smoke Detector Head