BlueWalker 10120174 Manual De Usuario

Descargar
Página de 60
25
Use cable cross section and protective device specification
                                   Model                                                     VFI 20000TP 3/3 BE/BI
  Rectifier Input L1, L2, L3, N, 
  Bypass Input L1, L2, L3, N, 
  min. conductor cross section[mm  ]                                                      6 
  max. possible cross section[mm  ]                                                       35
  Rectifier Input L1, L2, L3, N breaker (A)                                 60A 230VAC
  Bypass Input L1, L2, L3, breaker (A)                                        60A 230VAC
  Rectifier Input fuse (A)                                                              60A 250VAC
  Bypass Input fuse (A)                                                               60A 250VAC
  Output   L1, L2, L3, N, 
  min. conductor cross section[mm  ]                                                    6 
  max. possible cross section[mm  ]                                                     35 
  External Battery Cabinet Positive 
  pole(+),Neutral pole,Negative pole (-), 
  min. conductor cross section[mm  ]                                                   10 
  max. possible cross section[mm  ]                                                     35  
            80A 250VDC
80A 250VDC
  Protective Earthing conductor [mm  ]                                             Max 35
40A 250V AC Clearance 
distances:>=1.4mm  Break time<=15s
  Torque for fixing above terminals                                                 2.8-3 Nm
  Internal battery fuse                                                                 100A 700VAC
  External Battery Cabinet Fuse (A) in 
  Positive pole(+),Neutral pole,
  Negative pole (-),
External Battery Cabinet breaker (A) in Posi-
tive pole(+),Neutral pole,Negative pole (-),
  Backfeed protection device
2
2
2
2
2
2
2
Notice!
The following label must be displayed on all switching devices installed in the same 
electrical system as the UPS, even when these are located at a distance from the area 
in which it is located (according to European standard EN 62040-1-1).