GENERAL DATA
2-4
2.1.3.
CEILING CASSETE (RAI-25RPA/35RPA/50RPA)
INDOOR
Unit
RAI-25RPA
RAI-35RPA
RAI-50RPA
RAI-ECPP
Nominal capacity adjustable
-
-
-
Nominal Cooling capacity (min - max)
kW
2.5 (0.9-3.0)
3.5 (0.9-4.0)
5.0 (0.9-5.2)
Cooling sensible capacity
kW
2.0
2.9
3.8
Nominal Heating capacity (min - max)
kW
3.5 (0.9-5.0)
4.8 (0.9-6.6)
6.2 (0.9-7.6)
Noise level cooling (sound pressure)
(SL / L / M / H)
(SL / L / M / H)
dB(A)
25/29/32/35
26/29/34/39
29/32/35/43
Noise level heating (sound pressure)
(SL / L / M / H)
(SL / L / M / H)
dB(A)
27/30/33/36
29/32/36/40
30/32/36/43
Noise level (sound power)
dB(A)
50
58
58
Air flow cooling mode (SL / L / M / H)
m
3
/h
330/360/420/480
390/420/510/570 390/450/510/630
Air flow heating mode (SL / L / M / H)
m
3
/h
390/420/480/540
450/480/510/660 450/510/540/690
Fan Motor
W
25
25
25
Drain pump pressure lift
cm
11.5
11.5
11.5
Static pressure (SL / L / M / H)
(nominal conditions SP 00)
(nominal conditions SP 00)
Pa
-
-
-
Dehumidification
l/h
1.4
1.8
2.0
Included drain pump
yes
yes
yes
Max. height available for drain pump
(RAD/RAI only)
(RAD/RAI only)
115
115
115
Dimensions (H x W x D)
mm
285x580x580
285x580x580
285x580x580
32x650x650
Panel dimensions (H x W x D)
mm
32x650x650
32x650x650
32x650x650
Weight
kg
20.0
20.0
20.0
Colour (Munsell Code)
Optional panel (RAI-ECPP)
Pure White
(N9.25)
Condensate Drain
mm
φ16
φ16
φ16
Panel weight
kg
4.0
4.0
4.0
Panel reference
RAI-ECPP
RAI-ECPP
RAI-ECPP
Color of the panel (RAL)
RAL 9010
RAL 9010
RAL 9010
Running current
A
3.2~2.93 /
4.3~3.96
5.05~4.63 /
6.24~5.72
9.1~8.37 /
9.87~9.05
9.87~9.05
Power supply
35 V DC from
outdoor unit
35 V DC from
outdoor unit
35 V DC from
outdoor unit
Cable section
mm²
N/A
N/A
N/A
Piping diameter (Liq / Gas)
1/4" / 3/8"
1/4" / 3/8"
1/4" / 1/2"
Drain diameter (ext)
mm
φ16
φ16
φ16
Remote control (standard/optional) *
RAR-5E2/
SPX-RCDB
RAR-5E2/
SPX-RCDB
RAR-5E2/
SPX-RCDB
Filter
ACL Filter
Wasabi (Optional) Wasabi (Optional)
Wasabi (Optional)
Dimensions (H x W x D)
mm
35x270x5
35x270x5
35x270x5
Pre-filter (Standard / Optional)
Washable/-
Washable/-
Washable/-
*
more information regarding remote control can be found in Chapter 9
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the ISO 5151.
system, and are based on the ISO 5151.
2. The Sound Pressure Level is based on the following
conditions:
-
0.8 meter beneath indoor height center
-
1.5 meter from Discharge grille
The above data was measured in an anechoic
chamber so that reflected sound should be taken into
consideration when installing the unit.
chamber so that reflected sound should be taken into
consideration when installing the unit.
Operation Conditions
Cooling
Heating
Indoor Air Inlet Temperature
dB
27.0 °C
20.0 °C
WB
19.0 °C
Outdoor Air Inlet Temperature
dB
35.0 °C
7.0 °C
WB
6.0 °C
Piping Length: 5.0 meters; Piping Lift: 0 meter