C2G 16026 Manual De Usuario

Descargar
Página de 3
TECHNICAL 
MARKETING 
DOCUMENT
CAPACITY CHARTS & SPECIFICATIONS: 
Uniduct
®
 2700, 2800, 2900 Series Raceway
NOTE:
     Wire capacity is reduced to allow for proper conductor bend radius and maximum  
 
 permissible heat rise.
 
*  Category 6 augmented (6a) cable for 10Gigabit Ethernet – max allowed cable diameter 
per addenda No. 11 ANSI TIA/EIA 568-B.2. 
 
 Uniduct Series Raceway is not UL Listed and is only designed for use in protecting low    
 
 voltage wiring and cabling.
All Uniduct Latching Raceway are available in both  
6' and 8' [1.8m and 2.4m] lengths.
3/4" 
[19.1mm]
1 1/2" 
[38mm]
2900/2900L8
Uniduct 2900 Series Raceway Wire Fill Capacity Chart
O.D. (Approx. Dia.)
CABLE / WIRE SIZE
Inches
(mm)
40% FILL
UNSHIELDED 
TWISTED PAIR
4-pair / 24AWG Cat3
4-pair / 24AWG Cat5e
4-pair / 24AWG Cat6
4-pair / 24AWG Cat6a
25-pair / 24AWG
0.190
0.210
0.250
0.354
0.410
4.8
5.3
6.3
8.9
10.4
12
10
7
3
2
COAXIAL
RG6/U
0.270
6.9
6
FIBER
Zip Cord
Round 4 Strand Fiber
Round 6 Strand Fiber
0.118 x 0.236
0.187
0.256
3 x 6
4.8
6.5
12
12
6
1/2" 
[12.7mm]
1" 
[25mm]
2800/2800L8
Uniduct 2800 Series Raceway Wire Fill Capacity Chart
O.D. (Approx. Dia.)
CABLE / WIRE SIZE
Inches
(mm)
40% FILL
UNSHIELDED 
TWISTED PAIR
4-pair / 24AWG Cat3
4-pair / 24AWG Cat5e
4-pair / 24AWG Cat6
4-pair / 24AWG Cat6a
25-pair / 24AWG
0.190
0.210
0.250
0.354
0.410
4.8
5.3
6.3
8.9
10.4
4
3
2
1
1
COAXIAL
RG6/U
0.270
6.9
2
FIBER
Zip Cord
Round 4 Strand Fiber
Round 6 Strand Fiber
0.118 x 0.236
0.187
0.256
3 x 6
4.8
6.5
4
4
2
3/8" 
[9.5mm]
3/4" 
[19.1mm]
2700/2700L8
Uniduct 2700 Series Raceway Wire Fill Capacity Chart
O.D. (Approx. Dia.)
CABLE / WIRE SIZE
Inches
(mm)
40% FILL
UNSHIELDED 
TWISTED PAIR
4-pair / 24AWG Cat3
4-pair / 24AWG Cat5e
4-pair / 24AWG Cat6
4-pair / 24AWG Cat6a
25-pair / 24AWG
0.190
0.210
0.250
0.354
0.410
4.8
5.3
6.3
8.9
10.4
2
1
1
0
0
COAXIAL
RG6/U
0.270
6.9
1
FIBER
Zip Cord
Round 4 Strand Fiber
Round 6 Strand Fiber
0.118 x 0.236
0.187
0.256
3 x 6
4.8
6.5
2
2
1