Phoenix Contact Relay Module EMG 17-REL/KSR- 60/21-21-LC 2940414 2940414 Hoja De Datos

Los códigos de productos
2940414
Descargar
Página de 4
Nov 9, 2013    2 / 4
Technical data
Coil side
Operating voltage display
Yellow LED
Protective circuit
Bridge rectifier Bridge rectifier
Contact side
Contact type
Single contact, 2-PDT
Contact material
AgNi
Maximum switching voltage
250 V AC/DC
Maximum inrush current
6 A
Limiting continuous current
5 A
Interrupting rating (ohmic load) max.
120 W (at 24 V DC)
Interrupting rating (ohmic load) max.
95 W (at 48 V DC)
Interrupting rating (ohmic load) max.
60 W (at 60 V DC)
Interrupting rating (ohmic load) max.
40 W (at 110 V DC)
Interrupting rating (ohmic load) max.
55 W (at 220 V DC)
Interrupting rating (ohmic load) max.
1250 VA (for 250 V AC)
General
Test voltage relay winding/relay contact
4 kV AC (50 Hz, 1 min.)
Test voltage relay contact/relay contact
1 kV AC (50 Hz, 1 min.)
Operating mode
100% operating factor
Mechanical service life
Approx. 5 x 10
7
 cycles
Standards/regulations
IEC 60664
Standards/regulations
EN 50178
Standards/regulations
IEC 62103
Rated surge voltage / insulation
4 kV / Basic isolation, (safe isolation, reinforced insulation and 6
kV between input circuit and output contact current paths.)
Pollution degree
2
Surge voltage category
III
Mounting position
Any
Assembly instructions
In rows with zero spacing
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
4 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
8 mm
Screw thread
M3