Phoenix Contact Overvoltage protection for sub-distribution Arrester Type 1 / Type 2 for 5-wire connection Black-grey 2859712 Hoja De Datos

Los códigos de productos
2859712
Descargar
Página de 10
Nov 13, 2013    2 / 10
Technical data
General
Pollution degree
2
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
4
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 3.00
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
3L-N & N-PE
Protective circuit
IEC test classification
I + II
IEC test classification
T1 + T2
EN type
T1 + T2
Lightning protection class
I /100 kA (TT, TN-C-S)
Nominal voltage U
N
240 V AC (230/400 V AC ... 240/415 V AC)
Nominal voltage U
N
415 V AC (L-L)
Maximum continuous operating voltage U
(L-N)
350 V AC
Maximum continuous operating voltage U
C
 (N-PE)
350 V AC
U
T
 (TOV-proof)
415 V AC (5 s / L-N)
U
T
 (TOV-proof)
1200 V AC (200 ms / N-PE)
Nominal frequency f
N
50 Hz
Nominal frequency f
N
60 Hz
Rated load current I
L
125 A (≤ 55°C)
Residual current I
PE
≤ 5 µA (Residual current I
PE
)
Standby power consumption P
C
≤ 3.5 mW (≤ 150 mVA)
Power consumption without load Pc
≤ 3.5 mW
Nominal discharge current I
n
 (8/20) µs (L-N)
25 kA
Nominal discharge current I
n
 (8/20) µs (N-PE)
100 kA
Impulse discharge current (10/350) µs, charge
50 As
Impulse discharge current (10/350) µs, specific energy
2.50 MJ/Ω
Impulse discharge current (10/350) µs, peak value l
imp
100 kA
Impulse discharge current (10/350) µs, charge
50 As
Impulse discharge current (10/350) µs, specific energy
2.50 MJ/Ω
Impulse discharge current (10/350) µs, peak value l
imp
100 kA (N-PE)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
≤ 1.5 kV
Voltage protection level U
P
 (L-N)
≤ 1.5 kV
Voltage protection level U
P
 (N-PE)
≤ 1.5 kV
Residual voltage (L-N)
≤ 1.3 kV (at I
n
)
Residual voltage (L-N)
≤ 1.1 kV (at 10 kA)
Residual voltage (L-N)
≤ 1 kV (at 5 kA)
Residual voltage (L-N)
≤ 1 kV (at 3 kA)