Before connecting the unit to a power source,
the wire gauge must be taken into account.
Load wires must be large enough to resist
overheating when a short-circuit condition
occurs as well as to maintain a good regulation.
The size, polarity and length of a wire are all
factors in determining if a wire will withstand
short circuiting.
the wire gauge must be taken into account.
Load wires must be large enough to resist
overheating when a short-circuit condition
occurs as well as to maintain a good regulation.
The size, polarity and length of a wire are all
factors in determining if a wire will withstand
short circuiting.
Wires that are selected must be large enough to
withstand a short circuit and limit voltage
drops to no more than 2V per wire. Use the
table below to help make a suitable selection.
withstand a short circuit and limit voltage
drops to no more than 2V per wire. Use the
table below to help make a suitable selection.
AWG
Gauge
Conduct or
Diameter
mm
Diameter
mm
Ohms per
km
km
Max amps
for chassis
wiring
for chassis
wiring
0000
11.684
0.16072
380
000
10.4038
0.2027
328
00
9.26592
0.25551
283
0
8.25246
0.32242
245
1
7.34822
0.40639
211