International English                                                           8. SUPPLEMENTARY INFORMATION
106
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify
compliance of their apparatus with the EMC directive for the residential, commercial and
light industrial environment as regards the EMC performance characteristics of the power
drive system. Performance limits are as specified in the generic emission and immunity
standards EN 50081-1 and EN 50082-1.
Table 8-3
Class 3 - Filtered for Residential, Commercial and Light Industry
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions*
EN 55011
Level B
Conducted Emissions
EN 55011
Level B
Immunity:
Supply Voltage Distortion
IEC 1000-2-4 (1993)
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC 1000-2-1
Magnetic Fields
EN 61000-4-8
50 Hz, 30 A/m
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 2 kV control
Radio Frequency Electromagnetic Field,
amplitude modulated
ENV 50 140
80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
Radio-frequency Electromagnetic Field,
pulse modulated
ENV 50 204
900 MHz, 10 V/m 50% duty
cycle, 200 Hz repetition rate
* These limits are dependent on the inverter being correctly installed inside a metallic switchgear
enclosure. The limits will not be met if the inverter is not enclosed.
Notes
•  To achieve these performance levels, you must not exceed the default switching
frequency nor use cables longer than 25 m.
•  The MICROMASTER inverters are intended exclusively for professional
applications. Therefore, they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.
•  Maximum mains supply voltage when filters are fitted is 460V.