International English                                                                                            2. INSTALLATION
18
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
!
Warnings
♦  Work on the device/system by unqualified personnel or failure to comply with
warnings can result in severe personal injury or serious damage to material. Only
suitably qualified personnel trained in the setup, installation, commissioning and
operation of the product should carry out work on the device/system.
♦  Only permanently-wired input power connections are allowed. This equipment must
be grounded (IEC 536 Class 1, NEC and other applicable standards).
♦  If a Residual Current-operated protective Device (RCD) is to be used, it must be an
RCD type B.
♦  Machines with a three-phase power supply, fitted with EMC filters, must not be
connected to a supply via an ELCB (Earth Leakage Circuit-Breaker EN50178
Section 5.2.11.1).
♦  The following terminals can carry dangerous voltages even if the inverter is
inoperative:
- the power supply terminals L/L1, N/L2, L3.
- the motor terminals U, V, W, DC+, DC-
♦ Always 
wait 
5 minutes to allow the unit to discharge after switching off before
carrying out any installation work.
!
Caution
The connection of power, motor and control cables to the inverter must be carried out
as shown in Figure 2-4 on page 25, to prevent inductive and capacitive interference
from affecting the correct functioning of the inverter.
2.1 General
Installation after a Period of Storage
Following a prolonged period of storage, you must reform the capacitors in the inverter.
The requirements are listed below.
Period of Storage
Required Action
Preparation Time
1 year or less
No reforming required
No preparation
1 to 2 years
Apply power to the inverter for one hour before
issuing the run command
1 hour
2 to 3 years
 Use a variable AC supply
 Apply 25% of input voltage for 30 minutes
 Increase volts to 50% for a further 30 minutes
 Increase volts to 75% for a further 30 minutes
 Increase volts to 100% for a further 30 minutes
 Inverter ready for run signal
2 hours
3 years and over
 Use a variable AC supply
 Apply 25% of input voltage for 2 hours
 Increase volts to 50% for a further 2 hours
 Increase volts to 75% for a further 2 hours
 Increase volts to 100% for a further 2 hours
 Inverter ready for run signal
8  hours