3. COMMISSIONING                                                                                          International English
MICROMASTER 420 Operating Instructions
29
6SE6400-5AA00-0BP0
jog
0
1
P
Fn
Hz
RUNNING
P000
I = 4.8
fn
fl
p
v
F=
50.0
HZ
RPM=1500
V=400v
jog
0
1
P
Fn
menu
Status Display Panel
(Standard)
Basic Operator Panel
(Option)
Advanced Operator Panel
(Option)
Hz
150.00
3.1 
Front Panels for the MICROMASTER 420
Front panels
The front panels shown below are available for use with the MICROMASTER 420
Inverters. The panel on the left is supplied with the inverter as standard and is referred to
as the Status Display Panel (SDP). The Basic Operator Panel (BOP) and Advanced
Operator Panel (AOP) are available as options.
Figure 3-1
Panels available for the MICROMASTER 420 Inverter
Changing the front panel
The procedure for removing the SDP and fitting the BOP or AOP, which are available as
options, is described in Appendix A.
3.1.1 
 
Commissioning with the Status Display Panel (SDP)
The SDP is supplied with your MICROMASTER 420 Inverter as
standard. This panel has two LEDs on the front, which indicate
the operational status of the inverter.
With the SDP the inverter can be used with its default settings,
that covers a lot of applications. The default settings are shown
in Table 3.1
The terminal layout is shown in the photograph of the Control
Terminal Connections on the inside of the back cover of this
manual.
Table 3-1
Default settings for operation using the Status Display Panel
Terminals
Parameter
Default Operating
Digital Input 1
5
P0701 = ‘1’
ON right
Digital Input 2
6
P0702 = ‘12’
Reverse
Digital Input 3
7
P0703 = ‘9’
Fault Reset 
Output Relay
10/11
P0731 = ’52.3’
Fault Identification
Analogue Output
12/13
P0771 = 21
Output Frequency
Analogue input
3/4
P0700 = 0
Frequency Setpoint
1/2
Analog Input supply