International English                                                                             5. SYSTEM PARAMETERS
48
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
5.3 
System Parameters and Definitions
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
   Access Level
P0004 Setting
Changeable
Status
Drive Display
r0000
Displays the user selected output as defined in P0005.
Note:
Pressing the “Fn” button for 2 seconds allows the user to view the values of DC link
voltage, output current, output frequency, output voltage, and chosen r0000 setting (defined
in P0005).
-
-
[-]
-
1
7
Drive State
r0002
Displays the actual drive state.
Possible values:
0
“Commissioning Mode– (P0010 
≠ 0)”
1
“Ready to Run”
2
“Fault”
3
“Starting – DC Link Precharging”
4
“Running”
“Stopping – (ramping down)”
Note:
State 3 will only be visible while precharging DC Link and when externally powered
communications board is fitted.
0
5
[-]
-
2
7
User access level
P0003
Defines the access level into parameter sets.  For most simple applications the default
(standard) setting is sufficient.
Possible Settings:
0
“User defined parameter list – see P0013 (Level 3)
 
for details on use”
1
“Standard”:
allows access into most frequently used parameters
2
“Extended”:
allows extended access to inverter I/O functions
3
“Expert”:
for expert use only.
4
“Service”:
only for use by authorized service personnel –password protected.
0
4
[1]
-
1
All
'
•'