International English 5. SYSTEM PARAMETERS
86
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦
♦
♦P0003 User
Access Level
♦
♦
♦
♦
♦P0004 Setting
♦
♦
♦
♦Changeable
♦
♦
♦
♦Status
Fixed setpoint 5
P2205
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[40]
[40]
%
-
2
22
‘
•’
Fixed setpoint 6
P2206
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[50]
[50]
%
-
2
22
‘
•’
Fixed setpoint 7
P2207
Refer to the description in P2201 for Fixed Setpoint 1.
-130
130
[60]
[60]
%
-
2
22
‘
•’
Connector: Fixed PI Setpoint
r2224
Displays the total output of the PI fixed setpoint selection.
-130
130
[60]
[60]
%
-
2
22
Setpoint Memory of the Motorized Potentiometer (Keypad Setpoint)
P2231
0 = setpoint memory disabled.
1 = setpoint memory enabled.
If 0 is selected, the setpoint returns to the value set in P2240 after an OFF command. If 1 is
selected the active setpoint is remembered and P2240 is updated with the current value.
Refer to P2240.
selected the active setpoint is remembered and P2240 is updated with the current value.
Refer to P2240.
0
1
1
[0]
-
2
22
‘
•’
Inhibit keypad (Motorized Potentiometer) setpoint reverse direction
P2232
Inhibits the reverse setpoint selection when keypad (Motorized Potentiometer) is chosen
either as main setpoint or additional setpoint (using P1000)
either as main setpoint or additional setpoint (using P1000)
Possible settings:
0 Reverse direction is allowed – it is possible to change motor direction using the
keypad (Motorized Potentiometer) setpoint (increase / decrease frequency either by
using digital inputs or keypad up / down buttons)
using digital inputs or keypad up / down buttons)
1 Reverse
direction
inhibited
0
1
1
[1]
-
2
10
Keypad (Motorized Potentiometer) Setpoint
P2240
Allows the user to set a digital PI setpoint in %. The setpoint can be changed either by using
the
the
∆
∇
keys on the BOP or by setting P0702 or P0703 to 13 and 14.
-130
130
[10.00]
%
2
22
‘
•’
Active Digital PI output setpoint
r2250
Displays the active digital PI setpoint in %.
-130
130
[10.00]
%
2
22
‘
•’
P2253
Source: PI setpoint
0
2248.0
[0]
-
2
22
‘
•’