04/2003 System 
Parameters 
SINAMICS G110    Operating Instructions 
 
6SL3298-0AA11-0BP0 
55
 
5 System Parameters 
5.1  Introduction to SINAMICS G110 System 
Parameters 
The parameters can only be changed by using the optional Basic Operator Panel 
(BOP) or the Serial Interface. 
Parameters can be changed and set using the optional BOP to adjust the desired 
properties of the inverter, such as ramp times, minimum and maximum frequencies 
etc. The parameter numbers selected and the setting of the parameter values are 
indicated on the five-digit LCD display. 
 
Read only parameters are indicated with r instead of P. 
 
P0010 initiates “quick commissioning”. 
 
The inverter will not run unless P0010 is set to 0 after it has been accessed. 
This function is automatically performed if P3900 > 0. 
 
P0004 acts as a filter, allowing access to parameters according to their 
functionality. 
 
If an attempt is made to change a parameter that cannot be changed in this 
status, for example, cannot be changed whilst running or can only be changed 
in quick commissioning, then 
 will be displayed. 
 
Busy Message 
In some cases - when changing parameter values - the display on the BOP 
shows 
. This means the inverter is busy with tasks of higher priority.  
5.1.1 Access Levels 
There are three access levels available to the user; Standard, Extended and 
Expert. The level of access is set by parameter P0003. For most applications, the 
Standard and Extended levels are sufficient. 
The number of parameters that appear within each functional group (selected by 
P0004) depends on the access level set in parameter P0003. For further details 
regarding parameters, see the Parameter List.