Siemens SINAMICS G110 0.12 kW 1-phase frequency inverter, 230 Vac to , 6SL3211-0AB11-2BA1 6SL3211-0AB11-2BA1 Hoja De Datos
Los códigos de productos
6SL3211-0AB11-2BA1
04/2003 System
Parameters
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
55
5 System Parameters
5.1 Introduction to SINAMICS G110 System
Parameters
The parameters can only be changed by using the optional Basic Operator Panel
(BOP) or the Serial Interface.
Parameters can be changed and set using the optional BOP to adjust the desired
properties of the inverter, such as ramp times, minimum and maximum frequencies
etc. The parameter numbers selected and the setting of the parameter values are
indicated on the five-digit LCD display.
(BOP) or the Serial Interface.
Parameters can be changed and set using the optional BOP to adjust the desired
properties of the inverter, such as ramp times, minimum and maximum frequencies
etc. The parameter numbers selected and the setting of the parameter values are
indicated on the five-digit LCD display.
Read only parameters are indicated with r instead of P.
P0010 initiates “quick commissioning”.
The inverter will not run unless P0010 is set to 0 after it has been accessed.
This function is automatically performed if P3900 > 0.
This function is automatically performed if P3900 > 0.
P0004 acts as a filter, allowing access to parameters according to their
functionality.
functionality.
If an attempt is made to change a parameter that cannot be changed in this
status, for example, cannot be changed whilst running or can only be changed
status, for example, cannot be changed whilst running or can only be changed
in quick commissioning, then
will be displayed.
Busy Message
In some cases - when changing parameter values - the display on the BOP
In some cases - when changing parameter values - the display on the BOP
shows
. This means the inverter is busy with tasks of higher priority.
5.1.1 Access Levels
There are three access levels available to the user; Standard, Extended and
Expert. The level of access is set by parameter P0003. For most applications, the
Standard and Extended levels are sufficient.
The number of parameters that appear within each functional group (selected by
P0004) depends on the access level set in parameter P0003. For further details
regarding parameters, see the Parameter List.
Expert. The level of access is set by parameter P0003. For most applications, the
Standard and Extended levels are sufficient.
The number of parameters that appear within each functional group (selected by
P0004) depends on the access level set in parameter P0003. For further details
regarding parameters, see the Parameter List.